Omega Engineering Paperless Recorder RD8900 用户手册

下载
页码 54
 
47
4.7  Demo
 
 
The Demo mode is  a simulation mode used for demonstration purposes.  It will simulate 18 AI 
analog inputs, 18 Math., 6 DI digital inputs and 6 DO digital outputs.  The trends are simulated 
by SIN waves.  To start the Demo mode,  turn the power off and on.  To stop the Demo mode 
and return to real mode, connected with real inputs, turn the power off and on once more. 
 
 
4.8  A configuration example
  
 
Here is a process required for a paperless recorder with 3-channels of 4-20mA input, 6-relay 
outputs and Ethernet communication for real-time monitoring.  With, Analog input card AI183
not yet fitted into rear slot, set up 4-20mA input according to 2.3 Setup input and output 
cards, 
and then plug it into rear SLOT 1.  Plug 6-relay output card DO181 into rear SLOT 2. 
Do the wiring and installation onto panel.  Set up the extensive PC software Observer II to PC, 
then power on the recorder. Open the front cover at the bottom side, then 5 soft keys appear. 
Press Config key to do Configuration.  Press Enter key to get into Channel mode.  Do settings 
according to 4.1 Channel.  Define the names for each channel, choose Log speed 1S, Method 
Instant, Range 4.000∼20.000, Scale Unit  %, ScaleLo 0.00 and ScaleHi 100.00. Define the 
Event (alarm ) High alarm H for Channel 1, 2 & 3, then define Job1 with Log alarm.  Then, do 
the rest of the settings according to 4.2 Display4.3 Tools4.4 Instrument and 4.5 Clock. If 
the IP address of the recorder is fixed for Ethernet communication, (not automatically assigned 
by the server), then the user needs to define IP as User Defined. Then set up the IP address and 
Subnet Mask in 4.4 Instrument. The recorder is now ready for real-time monitoring and data 
acquisition.  
 
If the user needs no communication and wishes to read measured data from the CF card on a 
PC, then set up the basic software Observer I in the PC, and add a CF card reader on USB port 
of PC.  To read the configuration and measured data on CF card for the first time, it is 
necessary to press the 
Save key to save configurations first, and then press the Dump key to 
Dump measured data from the recorder to CF card before inserting it into the CF card reader.  
If any configuration has been changed, it is necessary to press both keys before inserting the 
CF card into the reader
.  If the configuration remains unchanged, to dump measured data press 
the Dump key, do not press Save key again. After that, the measured data can be seen in trend 
or Excel format on PC.  A 16 MB CF card is supplied free.