Open Collector Option 
 
Whenever a limit is reached an open collector output provides a 5 Vdc signal at 50ma. on the output 
connector, e.g... Limit 1 provides its 5 volt output signal between pins 1 and 2. 
 
Figure 2.  Open Collector Hookup Example 
 
 
 
 
 
 
 
 
 
 
 
HOLD FUNCTION 
 
The hold function allows to freeze the Process Variable reading in the display window indefinitely till the 
Hold pin is active. This function is activated by tying Hold pin (pin13) to the digital ground pin (pin 14) 
through a relay or switch. 
 
 
SAVING PARAMETER: 
 
DP3600 saves all the programmed parameters in an EEPROM (electrically erasable programmable read 
only memory). An EEPROM stores the programmed parameters even when the power is removed from the 
unit. However, it is important to note that if the parameters are being changed during setup, they must be 
saved in the EEPROM by pressing and holding RESET key till the display reads ‘SAVING’. If the 
parameters are NOT saved and the power is removed from the unit, any newly changed values will be lost   
(the unit will maintain the old values). 
 
 
POWER 
 
Power connection should be made to the three terminal connector as shown in figure 3.  Also, make note 
that it is very important  that the power line inputs and the power ground are not switched. Doing so will 
permanently damage the instrument. Refer to the drawing for proper connections. For convenience, the 
printed circuit board is labeled   L1    L2    GND  on the under side of three terminal power connector. 
 
For instruments with the 12Vdc power option, refer to Figure 3. 
 
NOTE: WHILE MAKING POWER CONNECTION TO THE UNIT, MAKE SURE  THAT AC 
POWER LINE L1 OR L2 IS NOT ACCIDENTALLY CONNECTED INTO THE GROUND 
(GND) TERMINAL. THIS WILL RESULT IN PERMANENT DAMAGE TO THE 
INSTRUMENT. 
 
DOUBLE CHECK THE CONNECTIONS BEFORE APPLYING  POWER!! 
Instrument
 
-OUTPUT
 
+OUTPUT
 
LOAD
 
Solid State Relay, 
LED, Buzzer etc.