National Instruments Field Point cFP-Al-110 用户手册

下载
页码 20
FP-AI-110 and cFP-AI-110
16
ni.com
Physical Characteristics
Indicators .......................................... Green POWER and 
READY indicators
Weight
FP-AI-110................................... 140 g (4.8 oz)
cFP-AI-110................................. 110 g (3.7 oz)
Power Requirements
Power from network module ............ 350 mW
Safety Isolation Voltage
Channel-to-ground isolation
Continuous ................................. 250 V
rms
, Measurement 
Category II
Dielectric withstand.................... 2,300 V
rms
 (test duration 
is 5 s)
Channel-to-channel isolation ............ No isolation between 
channels
Environmental
FieldPoint modules are intended for indoor use only. For outdoor 
use, they must be mounted inside a sealed enclosure.
Operating temperature ...................... –40 to 70 °C
Storage temperature .......................... –55 to 85 °C 
Humidity ........................................... 10 to 90% RH, 
noncondensing
Maximum altitude............................. 2,000 m; at higher altitudes 
the isolation voltage ratings 
must be lowered.
Pollution Degree ............................... 2
Shock and Vibration
These specifications apply only to the cFP-AI-110. 
NI recommends Compact FieldPoint if your application 
is subject to shock and vibration. 
Operating vibration, random 
(IEC 60068-2-64).............................. 10–500 Hz, 5 g
rms
Operating vibration, sinusoidal 
(IEC 60068-2-6)................................ 10–500 Hz, 5 g