AUTOMATIC TRANSFER SWITCH
 
LEHE4651-04  
 
6
 
 
CTS SERIES ACCESSORY DEFINITIONS (continued) 
 
LonWorks 
LonWorks Communication Module 
M1 
Single Phase Amp Meter (Analog) 
M2 
Three Phase Amp Meter (Analog) 
M90 
EPM2000 True RMS Digital Meter with display (Amps, Volts, 
Power, Energy, Power Factor and Frequency). 3 Line LED 
Display. 50/60 Hz Universal Operation. 1 or 3 phase. Standard 
Modbus RTU RS485 communications capability. 
M90A 
Includes Modbus communication card and factory wiring 
between EPM2000 and Modbus communication card. 
M90B 
Includes Modbus communication card, Ethernet communication 
adapter and factory wiring between EPM2000 and Modbus 
communication card. 
M91 
EPM6000 True RMS Digital Meter with display (Amps, Volts, 
Power, Energy, Power Factor and Frequency, THD). Certified 
energy and demand metering. Meets ANSI C12.20 and IEC  
687 Accuracy Classes. Front IrDA Port Laptop Connection. 
Standard Modbus RTU RS485 or DNP 3.0 communications 
capability. 
M91A 
Includes Modbus communication card and factory wiring 
between EPM6000 and Modbus communication card. 
M91B 
Includes Modbus communication card, Ethernet communication 
adapter and factory wiring between EPM6000 and Modbus 
communication card. 
Modbus 
Modbus RTU Communication Module 
N1 
Running Time Indicator – Door mounted 
N2 
Operation Counter – Door Mounted 
P1 
Engine Start Timer (adjustable to 6 seconds) 
P2 
Engine Start Timer – Extended time delay (adjustable to 
300 seconds) 
Q2 
Peak shave/remote load test/area protection – Relay (S.P.D.T.) 
(Need to specify voltage – 120 VAC, 24 VAC, 24 VDC – 120V 
default standard) 
Q3 
Inhibit transfer to emergency (Source 2) (load add relay) – Relay 
(S.P.D.T.) (Need to specify voltage – 120 VAC, 24 VAC,  
24 VDC – 120V default standard) 
Q7 
Inhibit transfer to normal (Source 1) – Relay (S.P.D.T.) (Need to 
specify voltage – 120 VAC, 24 VAC, 24 VDC – 120V default 
standard) 
R1-1/R1-3 
Over Voltage sensing for normal (Source 1) single (R1-1) 
or three (R1-3) phase 
R15/R15D 
Load Shed. Should Source 2 become overloaded, a signal can  
be given to switch to the Neutral position. 
 
 
 
 
R16 
Phase rotation sensing of Normal (Source 1) and         
 
Emergency (Source 2) 
R26/R26D 
Interruptible Power Rate Provisions. Allow transfer out 
of Source 1 position to Mid position or dead Source 2. 
Alarm and Pre-Signal circuit included. (Need to specify 
voltage – 120 VAC, 24 VAC, 24 VDC 
R50 
In Phase monitor between Normal (Source 1) and 
Emergency (Source 2) to allow transfer 
S5P 
Microprocessor activated auto/manual retransfer 
selector switch for transferring to Normal (Source 1) 
(includes microprocessor activated YN accessory) 
S12P 
Microprocessor activated auto/manual retransfer 
selector switch for transferring to Normal (Source 1) 
(includes microprocessor activated YN & YE accessory) 
S13P 
Microprocessor activated commit/no commit on 
transferring to Emergency (Source 2) (with 
enable/disable settings) 
S14K 
Keyed selector switch for retransfer to normal-test-auto 
SW1 
Auto/Off/Start Engine control selector – Door mounted 
(keyed or non-keyed operation available) 
SW2 
Auto/Off Engine control selector – Door mounted 
(keyed or non-keyed operation available) 
SW3 
Source Priority Selector Switch – Door mounted. Allows 
selection of Source 1 or Source 2 to be the Prime 
Source. Transfer Switch will transfer to selected Prime 
Source if that Source is available. (keyed or non-keyed 
operation available) 

Retransfer to Normal (Source 1) adjustable time delay 
T3/W3 
Pre-signal contact on transfer to Normal (Source 1) or 
Emergency (Source 2) during test 

Engine stop /cool adjustable cool down timer 
UMD 
Pre and post transfer output adjustable time range. 
Functions in both directions. Includes 2 circuits. 
(Additional circuits available). 
VI 
Voltage imbalance between phases (3 Phase only) 

Adjustable time delay on transfer to Emergency  
(Source 2) 
YEN 
Bypass transfer timers function (soft key switch in 
microprocessor)