Maretron ACM100 用户手册

下载
页码 24
 
ACM100 User’s Manual  
 
 
2.4.2.3  Three-Phase (Phase A, B, C) Connection 
 
 
 
Page 8 
 
 
Revision 1.2 
 
Figure 5 – Three-Phase Connection Diagram  
 
 
Use the following instructions when you are connecting the ACM100 to a three-phase “Wye” 
circuit connected via three hot wires and a single neutral (NOTE: Three-phase delta connected 
circuits are not supported by the ACM100). You will need to install three current transformers 
and three user-supplied voltage sense cables. The ACM100 comes with a single current 
transformer so you will need to purchase two optional current sensors (Part # PCT-1000-101-
03) for monitoring this type of system. 
 
Step 1: De-energize the AC Source. 
 
Step 2:
 The Current Transformer has black and white wires. Install the first Current 
Transformer as follows: 
a.  Connect the black wire to pin 7 (I
A+
) on the ACM100 
b.  Connect the white wire to pin 8 (I
A-
) on the ACM100 
c.  Disconnect the Phase A hot wire from the AC power source and place it through the 
hole in the Current Sensor such that the arrow on the Current Sensor points towards 
the AC power source. Then, reattach the Phase A hot wire to the AC power source. 
 
Step 3: Install the second Current Transformer as follows: 
a.  Connect the black wire to pin 9 (I
B+
) on the ACM100 
b.  Connect the white wire to pin 10 (I
B-
) on the ACM100 
Line (Phase A) 
Neutral 
U.S. 
120 Volts 
60Hz 
Europe 
220 Volts 
50Hz 
AC Sour
ce 
1 2 
5
4
3
6
7
8
9 10 11 12
Fus
e
 
V
A
Li
ne
 
V
A
N
eutr
al
 
Current 
Transducer
ACM100 Screw Terminals
V
B
Li
ne
 
V
C
Li
ne 
V
B
N
eutr
al
 
V
C
N
eutr
al
 
I
A+
 
I
A-
 
I
B+
 
I
B-
 
I
C+
 
I
C-
 
Fus
e
 
Current 
Transducer
Fus
e
 
Current 
Transducer
Line (Phase B) 
Line (Phase C)