Friedrich WE12D33 安装指导

下载
页码 43
WALLMASTER
 
Performance Testing Installation and Test Method
 
The following instructions only apply to laboratory test procedures and do not apply to actual product installation 
and operation. 
 
Maximum cooling capacity must be achieved in accordance with the following instructions: 
For maximum capacity and efficiency, air shall be sampled 4 to 6 inches away from the intake of the unit.  See images below: 
ANSI/ASHRAE Standard 16-1983 (RA 2009) Method of Testing for Rating Room Air Conditioners and Packaged 
Terminal Air Conditioners shall be adhered to when testing for obtaining cooling capacity and airflow quality for 
rating this room air conditioning unit. 
Indoor Sampling 
Device  
FRONT VIEW 
NOTE: Images of the sampler are for display purposes and not to scale 
TOP VIEW 
Indoor 
Sampling 
Device  
FRONT VIEW 
4.0” – 6.0” 
4.0” – 6.0” 
Indoor Sampling 
Device  
Outdoor 
Sampling 
Device  
Outdoor 
Sampling 
Device  
Indoor Sampling 
Device  
BACK VIEW 
Outdoor 
Sampling 
Device  
The indoor and outdoor air sampling devices must comply with: 
ASHRAE 41.1-1986 (RA 2006) - Method for Temperature Measurement 
ASHRAE 41.6-1994 (RA 2006) - Method for Measurement of Moist Air Properties 
® 
41