LG PQDSBC1 业主指南

下载
页码 14
11
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.  
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Figure 10: Setting the Mode Rotary Switch
Control
Mode
Rotary
Switch
Note:
The control source priority for the indoor unit is:
1. Central Controller
2. Dry Contact
3. Wired/Wireless Remote Controller
Control Mode: OFF (0)
Use this setting when the dry contact is installed but not used.
General Mode (1 - 6)
CONTROL_MODE_SW
Setting
Input A
Input B
Operating Mode Description
0
OFF
OFF
Dry contact function is off. No change in indoor unit operation.
ON
OFF
OFF
ON
ON
ON
CONTROL_MODE_SW
Setting
Input A
Input B
Operating Mode Description
1
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit prior operating condition maintained, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, locked
2
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit operating, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, locked
3
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit stopped, locked
OFF
ON
Indoor unit prior operating condition maintained, unlocked
ON
ON
Indoor unit operating, unlocked
INSTALLATION