Amana PTH073G35CXXX 目录

下载
页码 16
MC-DPTAC
www.amana-ptac.com
15
f
raming
 
for
 a
ccessory
 w
all
 s
leeve
 (ws9XX)
FINISHED FLOOR
42 1/4
"
16 1/4"
  MIN
MAIN STUD
JACK STUDS
HEADER - 4" x 4" OR
  DOUBLE 2"x 4" ON EDGE
SUB-FLOOR
CRIPPLE
JACK STUD
ADJUST FRAMING TO
 SECURE THIS DIMENSION
Wall sleeve opening height should be 
squared with wall sleeve opening width.
H = 16¼"
W = 42¼"
Fastening Wall Sleeve
When installed in an opening, the Wall Sleeve must be horizontally level (side-to-side) and pitched ¼ bubble to the outside.  
(NOTE: To ensure unit’s maximum efficiency, DO NOT over- or under-pitch.)
Installation Notes
1.  If Sub-base (PTSB***E) is installed, allow minimum 3¼” height clearance and maximum 5” height clearance between wall sleeve and floor; allow minimum 
2¾” protrusion from a finished wall. See Note 4 if using hydronic units.
2.  Drain Kit (DK900D) shipped separately. Can be mounted either right side, left side or bottom of sleeve. If mounted to bottom of sleeve, allow 2” height 
clearance from floor to bottom of sleeve.
3.  For UL approval, 265V units must use Amana
®
 brand Sub-base (PTSB***E) or Amana
®
 brand Hard Wire Kit (PSHW04A). Overcurrent protection on 265V 
units must be by cartridge-style time delay fuses, which are included and factory-installed on the Amana
®
 brand 265V chassis.
4.  If Hydronic Kit (HWK03 or HVK03) is installed, Wall Sleeve must extend exactly 3" into the room from the finished interior wall. If using the Amana
®
 brand 
Sub-base (PTSB***E), only the minimum 3¼” height clearance between wall sleeve and floor is permissible. Unit must also be operated with a remote-
mounted thermostat.
5.  If Duct Kit (MDK***) is installed, allow a minimum of 2⅜” into the room from the finished interior wall.
Mounting
Holes
(Drilled by 
Installer)
Plastic
Anchor
Screws
Expansion
Anchor Bolt
Toggle Bolt
Wood Screw
Alternative
Fastening Method
(Field Supplied)
Wall Sleeve must extend a minimum of ¼” beyond outside wall to allow for proper caulking.