DIAGNOSTIC CODES
C1
Indoor Coil is freezing up.
N
Y
Clean filter, Check for fan and blower operation,
Check for Refrigerant loss
or Restricted capillary tube.
C3
Indoor Coil is freezing up.
N
Y
Clean filter, Check for fan and blower operation,
Check for Refrigerant loss
or Restricted capillary tube.
C4
Indoor Coil froze up.
N
Y
Clean filter, Check for fan and blower operation,
Check for Refrigerant loss
or Restricted capillary tube.
C6
Poor Unit Performance.
N
Y
Check for blower motor, compressor,
or electr ic  heat operation.
C7
Indoor Freezing Lockout  (ICT  - IAT > 20) +10  Min
N
Y
Clean filter, Check for fan and blower operation,
Check for Refrigerant loss
or Restricted capillary tube.
RE
F
R
IG
E
R
A
T
IO
N
AL
E
RT
S
STATUS
DISPLAY
ERROR 
LIGHT
SUGGESTED ACTION
FP
Freeze Protection Engaged.  The  room temperature 
measured by the wireless remote thermostat or indoor ambient 
thermistor active  sensor falls below 40°F.
Y
N
No Action required. This setting will disengage when the 
room temperature  rises above 43°F.
Fd
Front Desk switch is closed. All outputs are switched off.
Y
N
Open front desk switch to allow occupant unit operation.
Eo
Un-Configured Service Board - 
All operation held awaiting configuration
Y
Y
Enter Configuration  Menu  and set "C3" to  "C"
for coolers with electric heat or "H" for heat pumps.
EH
Emergency Hydronic Engaged.  The EHH switch is closed.  
Compressor is switched off.
Y
N
Open front emergency hydronic switch to allow occupant 
unit operation.
LS
Load Shedding Engaged.  The LS switch is closed.  
Compressor and Electric heat is switched off.
Y
N
Open load shedding switch
to allow occupant unit operation.
On
Control is configured to respond to a wired thermostat
Y
N
No  action if a wired thermostat  is  being used.
Otherwise, see Configuration Settings.
oP
Open Door  Lockout
(DS1 & DS2 open; wireless)
Y
Y
Close Room Door.
Unit will not condition space with door open.
nP
Window Switch Lockout -
(LS & INN open)
Y
Y
Close Room  Door or Window.
Unit will not condition space with door or window open.
hP
Heat Sentinel -
(WIAT > u3)
Y
N
No action  required. This setting will  disengage when
the room temperature falls.
Ur
Un-Rented Status
(EHH  & INN or wireless)
Y
N
Front Desk needs to set to Rented mode (if applicable).
Indoor Ambient Thermistor reads outside the
range -20°F to 200°F & the wireless thermostat is not 
communicating  to the unit control  or
Indoor Ambient Thermistor (IAT) without a wireless remote 
thermostat reads outside the range -20°F to 200°F.
F2
Wireless Remote  Thermostat failure
N
N
Replace Wireless Thermostat.
F3
Indoor Ambient Thermistor reads
outside the range -20°F to 200°F
Y
N
Replace black Indoor Ambient Thermistor.
F4
Indoor Coil Thermistor either  above
or below operating tolerances.
N
Y
Replace Red Indoor Coil Thermistor .
F5
Wireless Thermostat  failure.
N
Y
Attempt to rebind Wireless Thermostat
or Replace Wireless Thermostat.
F6
Indoor Discharge Thermistor either above
or below operating tolerances.
N
Y
Replace Yellow  Indoor
Discharge Thermistor.
Fb
Low Remote Battery  Warning.
N
Y
Replace Batteries in Wireless Devices.
H1
High Voltage Protection engaged. 
Power supply voltage  is  to high.
Y
N
Check for incoming power at corr ect voltage.
br
Brown Out Protection engaged.
Power was lost or voltage is low.
N
N
Check for incoming power at corr ect voltage.
L6
Discharge Air Too Hot.
N
Y
Clean Filter or Remove Air Blockage.
LC
Outdoor Coil  Thermistor temperature high.
N
Y
Clean Condenser Coils, Check Fan for
fault. Code will reset  after cleaning.
C2
Indoor Air Recirculation.  Large delta between thermostat and 
return.
N
Y
Clean Filter or Remove Air Blockage or Close
Vent Door or Improve indoor to outdoor seal.
C5
Outdoor Coil  temperature too high  for outdoor ambient 
temperature.
N
Y
Check for Blocked Outdoor Air or Clean Coil.
Replace black Indoor Ambient  Thermistor  or 
Wireless Remote Thermostat.
Y
Y
F1
CODE
AI
R
F
L
O
W
 
AL
E
RT
S
F
A
IL
UR
E
S
M
O
DE
S