LG PMBD3640 数据表
Date:
JobName/Location:
PONo.:
Architect:
Engr:
GC:
Rep:
For:
File
Approval
Mech:
Resubmit
Other
Tag#:
(Company)
(ProjectManager)
PMBD3640
4ͲPortBranchDistributionUnit(BDUnit)
Page1of2
DFSͲSBͲGCͲ003ͲUS012K17
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com
Performance:
Electrical:
PowerSupply(V¹/Hz/Ø)
208Ͳ230/60/1
PowerInput(W)
10
RatedAmps(A)
0.1
Piping:
LiquidLine(in,OD)
3/8
VaporLine(in,OD)
3/4
PipingConnectiontoOutdoorUnit:
PipingConnectiontoIndoorUnit:
LiquidLine(in,OD)
1/4(Qty4)
VaporLine(in,OD)
3/8(Qty4)
UnitData:
NetWeight(lbs)
16
ShippingWeight(lbs)
18
CommunicationCabletoIDUs²(NoxAWG)
4x18
CommunicationCabletoODUs²(NoxAWG)
4x16
IDUͲIndoorUnitODUͲOutdoorUnit
StandardFeatures:
•Distributesrefrigeranttoindoorunits
•Internalcomponentsareinsulated
•FlarejointsprovidedforeasyinstallaƟon
•Compactdesign
Notes:
1.AcceptableoperaƟngvoltage:187VͲ253V.
2.AllcommunicaƟoncabletobeminimum18AWG,2Ͳconductor,stranded,shieldedand
mustcomplywithapplicablelocalandnationalcode.
mustcomplywithapplicablelocalandnationalcode.
3.Pipinglengths:
•MaximumheightdiīerencebetweenBDunitandindoorunitsͲ32.8Ō
•MaximumheightdiīerencebetweenBDunitandBDunitͲ49.2Ō.
•MaximumpipinglengthbetweenBDunitandindoorunitsͲ49.2Ō
4.TheBDunitshouldbeinstalledinsideofabuilding.
5.MustfollowinstallaƟoninstrucƟonsintheapplicableLGinstallaƟonmanual.
6.PowerwiringcablesizemustcomplywiththeapplicablelocalandnaƟonalcode.
MaxPortCapacityBtu/h(eachport)
24,000
MaxUnitCapacityBtu/h(sumofports)
72,000