Faber CLASSICA 规格说明表单
Rev. 07/11
Dimensional Diagrams & Electrical Knockouts
WARNING!
Product specifications are subject to change without notification. Consult the installation instructions before you begin installing this rangehood.
Make your ductrun as
straight and short as
possible. The ductrun
should not exceed 35
equivalent feet if ducted
with the required mini-
mum of 6” round duct.
Count 45º angles as 3
feet, 90º elbows as 5 feet,
and 90º flat elbows as 12
feet.
For best results, use
no more than three 90°
elbows. Make sure that
there is a minimum of
24” of straight duct
between elbows if more
than one is used. Do
not install two elbows
together. If you must
elbow right away, do
it as far away from the
hood’s exhaust opening
as possible.
straight and short as
possible. The ductrun
should not exceed 35
equivalent feet if ducted
with the required mini-
mum of 6” round duct.
Count 45º angles as 3
feet, 90º elbows as 5 feet,
and 90º flat elbows as 12
feet.
For best results, use
no more than three 90°
elbows. Make sure that
there is a minimum of
24” of straight duct
between elbows if more
than one is used. Do
not install two elbows
together. If you must
elbow right away, do
it as far away from the
hood’s exhaust opening
as possible.
Pre-Planning Your Installation -
Important: Consult the installation instructions before you begin installing this rangehood.
duc
tless
- ” min
15 3/4
”
max
18 1/4”
10 3/4
”
36”
x
also consult cooktop
manufacturer's recommendation
upper
chimney
lower
chimney
canopy
x = distance from hood to cooktop
(varies depending on installation)
min - 24”, suggested max - 30”
cabinet base
19 3/4
”
For shorter
ceilings, have
the chimney
cover(s) cut at
a sheet metal
shop. For
higher ceiling
installations, the
High Ceiling
Chimney Kit
includes a
new 39” upper
chimney which
would replace
the 15 3/4”
upper chimney
that came with
the hood.
min & max ceiling height examples
x = 30"
min
7'
11"
max
9'
2 3/4"
x = 28"
min
7'
9"
max
9'
3/4"
x = 26"
min
7'
7"
max
8'
10 3/4"
x = 24"
min
7'
5"
max
8'
8 3/4"
duc
tless:
Note: for ductless installations, subtract 3 1/2" from the
minimum ceiling height