OceanAire 2OACH3634 手册

下载
页码 36
CONDENSATE RESERVOIR TANK 
 
For Models 2OACH12, -18, -24 -36, a 5-gallon polyethylene tank is provided standard, to 
collect condensate.   The tank is located in the lower, front section of the unit. A high 
water level cut-out switch is used to stop the compressor and condenser fan automatically 
when the tank's pre-set water level has been reached. The evaporator fan will continue to 
run, circulating air. The control display will read “CON” 
TANK LEVEL ADJUSTMENT INSTRUCTIONS 
 
An adjustment screw is provided to vary the cut-off of the tank full switch. If a lighter (less 
weight) level of water is desired, turn the adjusting screw clockwise. Do not exceed 6 full 
turns counter-clockwise. 
 
CAUTION, TURN UNIT OFF:  BEFORE ADJUSTING SET SCREW 
   BEFORE 
REMOVING 
TANK 
TO 
EMPTY 
CONDENSATE 
 
Turn screw clockwise to lower water level. Less water makes tank lighter and easier to 
remove. 
 
NOTE:  Max. and Min. water levels shown are those at which the unit will shutdown and 
not restart until the condensate tank has been drained. 
Condensate Tank 
 
*Tank Water Level 
Adjusting Screw 
 
Spring 
Handle 
High Water Level  
Cut-Out Switch 
 
Condensate  
Tank Tray 
Max Water 
Level 
4" From Top 
For 2OACH12, 2OACH18, 2OACH24 
and 2OACH36, condensate water 
drops from drain pan into trough on 
tank