ATTRIBUTES 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
28 
 
In Fig. 15, the attribute "Operating Mode" is set to "Manual", i.e. the value entered 
manually is processed in the application program. 
 
NOTE: 
“Value” and “Manual Value” are online attributes, relevant only during controller 
operation via MMI or XL-Online. Furthermore, “Manual Value” is an internal online 
attribute only, not visible to the operator! The operator will see only the online 
attribute “value”, which can be edited only if the attribute "Operating Mode" is set to 
"Manual". See also section "Operating Mode" on page 29. 
 
 
Network Variable (V2.04.xx or higher) 
Datapoints which are mapped to network variables on the L
ON
W
ORKS
 network have 
an attribute named "Network Variable" containing the network variable index (0-
4095) and the network variable name which allows this information to be displayed 
on an MMI. 
 
 
Normally Open/Normally Closed (V2.04.xx or higher) 
The attribute "Normally Open/Normally Closed" defines the relationship between 
the input/output signal of a digital datapoint and its logical status. This attribute is 
also applicable when the digital point is the basic point of a flexible datapoint. 
 
NOTE:
 
The attribute "Active State" is fixed at 1 and is no longer relevant for 
applications designed for this controller firmware version. Applications 
designed for an older controller version will still work with this firmware 
though, and in that case the attribute "Active State" is still active. 
 
Table 11 and Table 12 show the relationship between the I/O signals, the attributes, 
and the logical status for digital inputs and digital outputs, respectively. 
 
Table 11. The attribute " Normally Open/Normally Closed " – Digital Inputs 
 
input signal 
NO/NC attribute 
logical status 
text displayed 
Low (<2.5 V) 
N.O. 
passive 
High (>5 V) 
N.O. 
active 
Low (<2.5 V) 
N.C. 
active 
High (>5 V) 
N.C. 
passive 
 
Table 12. The attribute " Normally Open/Normally Closed " – Digital Outputs 
 
output signal 
NO/NC attribute 
logical status 
text displayed 
Low (<2.5 V) 
N.O. 
passive 
High (>5 V) 
N.O. 
active 
Low (<2.5 V) 
N.C. 
active 
High (>5 V) 
N.C. 
passive 
 
In the open LON mode, the "Normally Open/Normally Closed" functionality is 
supported from CARE 5.0 and controller firmware 2.06.05 onwards. 
 
 CAUTION 
Regarding “Normally Open/Normally Closed,” the behavior of controllers 
with OS < 2.06.05 engineered using CARE 4 differs significantly from 
controllers with OS 2.06.05 and higher engineered using CARE 7 and 
higher. See also section “Controller OS 2.06 usage and functionality in 
CARE 4 and CARE – XL500 7.01.02” in Excel CARE – User Guide (EN2B-
0182GE51).