ALARM HANDLING 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
46 
 
 
Operational status 
All datapoints can be switched from the 'automatic' to the 'manual' operational 
mode. Each time the operating mode is changed, irrespective of the direction 
involved, a critical alarm signal is generated. Both alarm signal texts are 
preprogrammed and require no input from the user. 
 
Remote (V2.0.x) (not with Excel 100C) 
If a manual override control is changed on a Distributed I/O module, an alarm 
“overr.switch_manu” or “overr.switch_auto” is generated and the “manu” value is 
transmitted. 
 
 Alarm suppression in manual mode 
Under controller firmware 2.06.02 and higher, the following datapoint alarms can be 
suppressed for as long as the corresponding datapoints are in the 'manual override' 
mode: 
 
• 
min. and max. limit alarms (of analog datapoints, only); 
• 
status alarms (of digital datapoints, only). 
 
This alarm suppression is activated during CARE engineering by inserting the "at" 
sign ("@") at the beginning of the descriptor text of the pseudo datapoint "Startup". 
 
Benefits: 
As long as this alarm suppression is in effect, the repair or replacement of defective 
and/or malfunctioning (flickering) inputs (resulting e.g. from sensor breakage, 
sensor short-circuiting, defective alarm switches, etc.) can be performed while the 
corresponding datapoint is in the "manual override" mode. 
 
NOTE:
 
Only when using XFI 2.1.0 SIM1 will the event behavior and visualization 
behavior be identical to that of Honeywell Deltanet controllers. 
 
 
System Alarms 
 
 
Operating errors that occur in a control unit or during communication with other 
Excel 50/100/500/600/800 units are recognized and displayed by the computer 
module. These alarm signals can relate, for example, to a defective module, the 
need to change the buffer battery (data protection), or the presence of one digital 
output module too many (maximum 10). These alarm signal texts are 
preprogrammed. They are always critical alarms. 
 
Table 20. System alarms 
 
Alarm 
no. 
alarm text 
English) 
cond. 
code # 
cause/reason 
                                                                                                                               
AI Module Defect 
25 
Maximum conversion time was exceeded while testing ADC (defect on an AI card). 
AI 0 Volt Error 
24 
While measuring GND voltage on an AI card, one value greater than 0.5 V was measured 
(AI card defect). 
AI 5 Volt Failure 
23 
While measuring the 5-V reference voltage on an AI card, one value greater than 5 V or 
smaller than 4.5 V was measured (AI card defect or incorrect power supply of AI card). 
MAX 2 alarm 
Alarm limit for AI-, PA points 
MAX 2 normal 
76 
Alarm limit for AI-, PA points 
MAX 1 alarm 
Alarm limit for AI-, PA points 
MIN 2 alarm 
Alarm limit for AI-, PA points 
MIN 2 normal 
78 
Alarm limit for AI-, PA points 
MIN 1 alarm 
Alarm limit for AI-, PA points 
10 
MAX 1 normal 
75 
Alarm limit for AI-, PA points 
11 
MIN 1 normal 
77 
Alarm limit for AI-, PA points 
12 
Alarm memory full 
22 
1) After starting the Field I/O Task with the parameter "INIT", the default datapoint 
description couldn't be installed because USX didn't provide enough storage space for 
sending CNAP telegrams. 
2) Alarm send buffer full. 
13 
Alarm 
Alarm condition control for DI , PD points.