TROUbLEShOOTING
Continued 
 WARNING: If you smell gas
•  Shut off gas supply.
•  Do not try to light any appliance.
•  Do not touch any electrical switch; do not use any phone in your 
building.
•  Immediately call your gas supplier from a neighbor’s phone. Fol-
low the gas supplier’s instructions.
•  If you cannot reach your gas supplier, call the fire department.
POSSIBLE CAUSE
1. Pilot flame may be too low 
to sense flame causing igni-
tion module to shut down
2. Improper  venting,  exces-
sive blockage, or high wind 
conditions. Overdrafting of 
straight (no offset) vertical 
vent systems over 15 feet in 
height.
1. Metal expanding while heat-
ing  or  contracting  while 
cooling
1. Residues from manufacturing 
processes and logs curing
1. Gas  leak.  See  Warning 
statement  at  top  of 
page
2. Control valve defective
1. Flame impingement on logs 
and burner
2. Gas  leak.  See  Warning 
statement  at  top  of 
page
1. Improper log placement
2. Air  holes  at  burner  inlet 
blocked
3. Burner flame holes blocked
4. Improper venting or exces-
sive blockage
5. Excessive amounts of em-
bers and pan material
OBSERvED PROBLEM
Frequent outage of main burner 
and pilot after complete ignition 
sequence.
Fireplace produces a clicking/
ticking noise just after burner 
is lit or shut off
Slight  smoke  or  odor  during 
initial operation
Gas  odor  even  when  control 
knob is in OFF position
Glass soots
Dark residue on logs or inside 
of fireplace
REMEDY
1. Clean and adjust pilot flame for 
maximum  flame  across  sensor 
rod.
2. Have vent system inspected, includ-
ing the termination cap. Remove 
any restriction or obstruction. Add 
restrictor plate model VR-58 in 
straight  vertical systems over 15 
feet (if not previously installed)
1. This is common with most fireplac-
es. If noise is excessive, contact 
qualified service person
1. Problem will stop after a few hours 
of operation
1. Locate and correct all leaks (see 
Checking Gas Connections, page 
28)
2. Replace gas conrol valve
1. Adjust the log set that the flame 
does not excessively impinge on 
log surfaces
2. Inspect the opening at the base of 
the burner to see that it is NOT 
packed with any type of material
1. Properly locate logs (see Install-
ing Logs, Lava Rock, and Glowing 
Embers, page 30)
2. Clean out air holes at burner inlets, 
Periodically repeat as needed
3. Remove  blockage  or  replace 
burner
4. Have the vent system inspected, 
including the termination cap. Re-
move any restrictions or blackage
5. Clear excess embers from around 
the rear main ports. Use a mini-
mum of one layer of smaller ember 
peices to acheive the best glowing 
effect over the visible areas