Pre-Installation
1.  Visually inspect the CWBT for any damage. If damage exists 
return product for replacement.
Installation
This  product must be installed by a 
qualified professional.
1. Refer to Figure 1 for typical installation of the AMTROL 
CWBT Series.
Maintenance
1.  A qualified professional should check the complete system,
including the CWBT, yearly and more frequently as the 
system ages.
Operation
1.  The CWBT models are designed to add capacity to non-
potable, closed, chilled water systems to help reduce 
compressor unit cycling, improve temperature control and 
provide more consistent system operation.
2.  Water temperature is not to exceed 450°F.
3. System pressure is not to exceed the maximum working 
pressure of the tank.
Warranty
CWBT120-3 through CWBT1040-12 Models
:
One (1) Year Limited Warranty
Visit www.amtrol.com for complete warranty details.
Chlorine & Aggressive Water. The water quality 
can significantly influence the life of this product. 
You should test for corrosive elements, acidity, total solids and other 
relevant contaminants, including chlorine and treat your water appropriately 
to insure satisfactory performance and prevent premature failure.
Welding to the pressure vessel boundary will 
void the ASME rating.
Leaking, corrosion or indications of damage are 
signs of an impending serious failure of the 
buffer tank. Periodically inspect for damage and if noted the product 
must be serviced or replaced. Failure to follow these instructions 
could result in serious personal injury or death and 
 
property damage.
Water temperature above 100°F can be very 
hazardous. Allow system water temperature to 
cool down below 100°F before blowing down this product. Failure to 
follow these instructions could result in serious personal injury or 
death and property damage.
EXPLOSION OR RUPTURE HAZARD. A relief 
valve must be installed to prevent pressure in 
excess of local code requirement or maximum working pressure 
designated in the Product Manual, whichever is less. At least once every 
3 years or if discharge is present, a licensed contractor should inspect the 
temperature and pressure relief valve and replace if corrosion is evident 
or the valve does not function.
 FAILURE TO INSPECT THIS VALVE AS 
DIRECTED COULD RESULT IN UNSAFE TEMPERATURE OR 
PRESSURE BUILD-UP WHICH CAN RESULT IN PRODUCT FAILURE, 
SERIOUS INJURY OR DEATH AND/OR SEVERE PROPERTY 
DAMAGE AND VOID THE PRODUCT WARRANTY.
PUMP
BUFFER
TANK
OTHER VALVES AND ACCESSORIES REQUIRED FOR SYSTEM INSTALLATION ARE NOT SHOWN.
CHILLER
AIR
HANDLER
PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY
IMPORTANT GENERAL SAFETY INFORMATION - 
ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.
© 2015 AMTROL Inc. 
Part #: 9017-156 (01/15)
Mark of the
Originator
1400 Division Road, West Warwick, RI  USA 02893  
T: 800.426.8765    F: 800.293.1519
www.amtrol.com
Figure 1