Specifications
 
900-0112-01-00 Rev B  
51
 
Table 21 
24-Volt Inverter Settings (MATE3) 
Field Item Default 
Minimum 
Maximum 
Sensitivity (see page 14 for increments) 
6 0  50 
Pulse Length 
8 4  20 
Search 
Pulse Spacing 
60 AC cycles 
4 AC cycles 
120 AC cycles 
Input Type 
Grid 
Grid or Gen 
Input Support 
Y 
Y or 
Grid Input AC Limit 
25 Aac 
2.5 Aac 
30 Aac 
Gen Input AC Limit 
25 Aac 
2.5 Aac 
30 Aac 
AC Input and 
Current Limit 
Charger AC Limit  
5.5 Aac 
0 Aac 
6 Aac 
LowerVoltage Limit 
208 Vac 
140 Vac 
220 Vac 
Upper Voltage Limit 
252 Vac 
250 Vac 
280 Vac 
Grid AC Input 
Voltage Limits 
Transfer Delay  
6 AC cycles 
0 AC cycles 
240 AC cycles 
LowerVoltage Limit 
208 Vac 
140 Vac 
220 Vac 
Upper Voltage Limit 
252 Vac 
250 Vac 
280 Vac 
Transfer Delay  
6 AC cycles 
0 AC cycles 
240 AC cycles 
Gen AC Input 
Voltage Limits 
Connect Delay 
0.5 minutes 
0.2 minutes 
15 minutes 
AC Output 
AC Output 
230 Vac 
210 Vac 
250 Vac 
Cut-Out Voltage 
21 Vdc 
18 Vdc 
24 Vdc 
Low Battery  
Cut-In Voltage 
25 Vdc 
20 Vdc 
28 Vdc 
Absorb Voltage 
28.8 Vdc 
26 Vdc 
32 Vdc 
(Absorb) Time  
1.0 hours 
0.0 hours 
24.0 hours 
Float Voltage 
27.2 Vdc 
24 Vdc 
30 Vdc 
(Float) Time  
1.0 hours 
0.0 hours 
24.0 hours 
Battery Charger 
Re-Float Voltage 
25 Vdc 
24 Vdc 
26 Vdc 
Equalize Voltage 
29.2 Vdc 
28 Vdc 
34 Vdc 
Battery Equalize 
(Equalize) Time  
1.0 hours 
0.0 hours 
24.0 hours 
Aux Mode 
Cool Fan 
Remote, Load Shed, Gen Alert, Fault, Vent Fan, 
Cool Fan, Divert DC, Divert AC, or AC Drop 
(Load Shed) Enable Voltage 
22 Vdc 
20 Vdc 
28 Vdc 
(Gen Alert) ON Voltage 
22 Vdc 
20 Vdc 
28 Vdc 
(Gen Alert ON) Delay 
4 minutes 
0 minutes 
240 minutes 
(Gen Alert) OFF Voltage 
28 Vdc 
24 Vdc 
36 Vdc 
(Gen Alert OFF) Delay 
9 minutes 
0 minutes 
240 minutes 
(Vent Fan) Enable Voltage 
26 Vdc 
20 Vdc 
32 Vdc 
(Vent Fan) Off Period 
5 minutes 
0 minutes 
30 minutes 
(Divert DC or AC) Enable Voltage 
29.2 Vdc 
24 Vdc 
32 Vdc 
Auxiliary 
Output
 
(Divert DC or AC) Off Delay 
30 seconds 
0 seconds 
240 seconds 
Inverter 
Stacking 
Stack Mode 
Master 
Master, OB Slave L1, 3p Classic B , 3p Classic C 
Master Adjust Only 
0 0  7 
Power Save  
Slave Adjust Only 
1 1  15 
Grid Tie Enable 
Y  
Y or N 
Sell Voltage 
23.6 Vdc 
20 Vdc 
30 Vdc 
Grid-Tie Sell 
Grid Tie Window 
IEEE  
IEEE or user 
Input Voltage
9
 
-1 -3  1 
Output Voltage
9
 
-1 -3  1 
Calibrate 
Battery Voltage
10
 
0.0 -0.4  0.4 
 
                                                               
9
  These values represent an adjustable setting with a total range of 4 Vac.  The default value of -1 means the calibration will subtract 1 volt from the measured 
value.  The range of settings allow up to 1 volt to be added to the measured value, or up to 3 volts to be subtracted from it.  The result is also displayed.
 
10
 
These values represent an adjustable setting with a range of  ± 0.4 Vdc from the measured value.  The range of settings allow up to 0.4 volts to be either added 
or subtracted from the measured value (in increments of 0.2 Vdc).  The result is also displayed.