Heat Controller A-13 用户手册

下载
页码 56
WARNING
!
COOLING TROUBLE SHOOTING CHART
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE
TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM
POSSIBLE CAUSE
REMEDY
Unit will not run
• Power off or loose electrical connection
Check for correct voltage at compressor contactor in control
box
• Thermostat out of calibration-set too high
Reset
• Failed contactor
Check for 24 volts at contactor coil - replace if contacts are
open
• Blown fuses
Replace fuses
• Transformer defective
Check wiring-replace transformer
• High pressure control open (if provided)
Reset-also see high head pressure remedy-The high pressure
control opens at 610 PSIG
• Interconnecting low voltage wiring damaged
Replace thermostat wiring
Condenser fan runs, compressor
• Run or start capacitor failed (single phase only)
Replace
doesn’t
• Start relay defective 9single phase only)
Replace
• Loose connection
Check for correct voltage at compressor -
check & tighten all connections
• Compressor stuck, grounded or open motor winding
Wait at least 2 hours for overload to reset.
open internal overload.
If still open, replace the compressor.
• Low voltage condition
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
• Low voltage condition
Add start kit components
Insufficient cooling
• Improperly sized unit
Recalculate load
• Improper airflow
Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge
Charge per procedure attached to unit service panel.
• Air, non-condensibles or moisture in system
Recover refrigerant, evacuate & recharge, add filter drier
• Incorrect voltage
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
Compressor short cycles
• Incorrect voltage
At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
• Defective overload protector
Replace - check for correct voltage
• Refrigerant undercharge
Add refrigerant
Registers sweat
• Low evaporator airflow
Increase speed of blower or reduce restriction - replace air
filter
High head-low vapor pressures
• Restriction in liquid line, expansion device or filter drier
Remove or replace defective component
• Flow check piston size too small
Change to correct size piston
• Incorrect capillary tubes
Change coil assembly
• TXV does not open
Replace TXV
High head-high or normal vapor
• Dirty condenser coil
Clean coil
pressure - Cooling mode
• Refrigerant overcharge
Correct system charge
• Condenser fan not running
Repair or replace
• Air or non-condensibles in system
Recover refrigerant, evacuate & recharge
Low head-high vapor pressures
• Defective Compressor valves
Replace compressor
• Incorrect capillary tubes
Replace coil assembly
Low vapor - cool compressor -
• Low evaporator airflow
Increase speed of blower or reduce restriction - replace air
iced evaporator coil
filter
• Operating below 65°F outdoors
Add Low Ambient Kit
• Moisture in system
Recover refrigerant - evacuate & recharge - add filter drier
High vapor pressure
• Excessive load
Recheck load calculation
• Defective compressor
Replace
Fluctuating head & vapor
• TXV hunting
Check TXV bulb clamp - check air distribution on coil - replace
pressures
TXV
• Air or non-condensibles in system
Recover refrigerant, evacuate & recharge
Gurgle or pulsing noise at
• Air or non-condensibles in system
Recover refrigerant, evacuate & recharge
expansion device or liquid line
Circulating air blower & inducer
• Manual reset overtemperature control
Reset or replace
run continuously,
• tripped
compressor will not start
• Wire loose in limit circuit
Check wiring
51