8 - VENT DAMPER OPERATION
Figure 8 - Vent Damper Installation
Figure 9 - Vent Damper Placement
Annually check vent damper and all fl ue product 
carrying areas of appliance, with particular attention 
given to deterioration from corrosion or other 
sources.  If you see corrosion or other deterioration, 
contact your heating contractor for repairs.  Check 
vent damper operation as follows:
•  When boiler is off, check vent damper positions 
indicator points to closed position, Figure 10.
•  Turn thermostat or controller up to call for heat and 
check vent damper indicator points to open position.
•  Turn thermostat or controller down again and check 
damper position indicator returns to closed position.
Vent Damper Manual Operation
Vent damper may be placed in open position to 
permit burner operation by using “HOLD DAMPER 
OPEN” switch, located on damper controller.  
Thermostat will control burner fi ring as before, while 
damper will remain open.  DO NOT turn damper 
open manually or motor damage will result.  Set 
switch to “AUTOMATIC OPERATION” to close vent 
damper during burner off cycle.
For further information, and vent damper 
troubleshooting guide, refer to manual packaged with 
vent damper.
Inspect vent damper at least once a year by a 
qualifi ed service technician.  