6 - CONNECTING SUPPLY AND RETURN PIPING
RELIEF VALVE
DISCHARGE 
LINE
Check local 
codes for 
maximum 
distance 
from fl oor 
or allowable 
safe point of 
discharge
.
WARNING
Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns, 
scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:
• connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum 
distance from fl oor or allowable safe point of discharge;
• be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge 
line;
• have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or 
place any obstruction in discharge line;
• terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;
• allow complete drainage of the valve and the discharge line;
• be independently supported and securely anchored to avoid applied stress on the relief valve;
• be as short and straight as possible;
• terminate with plain end (not threaded);
• be constructed of material suitable for exposure to temperatures of 375°F (191°C); or greater.
Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation 
requirements.
!
   
Figure 2 - Safety Relief Valve