START-UP CHECKLIST
A. Project Information:
Start-Up Performed By ____________________________
Name __________________________________________________
Job Name ______________________________________________
ERV Unit Designation ____________________________________
Phone Number __________________________________________
Design Information
Application
Coupled to rooftop unit or stand-alone.
CFM
External Static Pressure
Supply Discharge
Down or horizontal (use horizontal for mated application)
Return Discharge
Down or horizontal (use horizontal for mated application)
Voltage/Phase
ERV Unit Part Number
Specify Rooftop Unit.
NOTE: Complete This Section for Coupled Applications Only
Model Number
HVAC Unit Discharge Type
Down discharge or horizontal discharge.
Roof Curb (Option)
Yes
No
14-in. Tall Roof Curb
Field install
Vibration Isolation Curb
Field install
Transition (Option)
NOTE: Complete This Section for Coupled Applications Only.
Rooftop Unit Discharge
Down or horizontal discharge rooftop unit.
Percent Outside Air
Outside air thru ERV unit as a percent of total rooftop unit cfm.
Transition Part Number
Field install
Inside Mounting Kit (Option)
Yes
No
NOTE: Complete This Section for Indoor Applications Only.
Factory installed
Removes rainhoods and adds duct flanges.
Electrical Disconnect (Option)
Yes
No
Fused
Factory installed
Switched
Factory installed
Two-Position Motorized Dampers (Option)
Yes
No
Outside Air Damper
Factory installed
Exhaust Air Damper
Factory installed
Economizer (Accessory for Rooftop Unit)
Yes
No
NOTE: Do Not Use With Wheel Bypass Option.
Field install
Special economizers required for some rooftop units. See the price pages.
Wheel Bypass With Stop Jog Control (Option)
Yes
No
NOTE: Do Not Use With Economizer Option.
Factory installed
Stops the ERV wheel rotation for free-cooling.
Stop Jog Control (Option)
Yes
No
NOTE: Use With Economizer Option.
Factory installed
Jogs the wheel during economizer mode to expel contaminants.
Pre-Heater (Option)
Yes
No
kW
Factory installed
Temp Control
Temp and Static Pressure Control
Frost Protection (Option)
Yes
No
NOTE: Do Not Use With Pre-Heater.
Factory installed
Defrosts wheel with exhaust air, by shutting down OA blower.
Low Temperature Lock Out (Option)
Yes
No
Factory installed
Shut down ERV unit at low temperature set point.
Filter Maintenance Indicator (Option)
Yes
No
Factory installed
Senses static pressure across OA filters (can be set for return filters).
ERV Blower Maintenance Indicator (Option)
Yes
No
Factory installed
Monitors OA and EA blowers and sends signal on electrical spike.
ERV Wheel Maintenance Indicator (Option)
Yes
No
Factory installed
Monitors ERV wheel and sends signal on electrical spike.
Airflow Monitor (Option)
Yes
No
Factory installed
Gages display static pressure across wheel for OA and exhaust air.
ERV Control Timer (Option)
Yes
No
24 Volt Mounted in ERV
Factory installed
24 hour / 7 day timer mounted in ERV unit.
115 Volt Remote Mount
Field install
24 hour / 7 day timer field mounted in remote location.
VAV Control (Option)
Yes
No
Factory installed
Provides independent VFD control for both OA and exhaust air.
CO
2
Sensor (Option)
Yes
No
Wall Mount or Duct Mount
Field install
Duct Mount With External View
Field install
For 62M040 Cabinet Only
Yes
No
Equipment Support
Field installed
Use for coupled applications.
Base Rail Option
Factory installed
Must be ordered when 62M040 sits on a roof curb.
Hinged Door Option
Factory installed
Provides hinges and latches on both access doors.
2-in. Filters Option
Factory installed
Replaces the standard 1-in. filters with 2-in. high efficiency, pleated.
Door Interlock Safety Switches
Factory installed
Cuts power to ERV unit when access doors are opened during operation.
Test Port Option
Factory installed
Allows for convenient monitoring of static / airflow across ERV wheel.