Wiring (continued)
TrueFRESH™ ERV/HRV Ventilation Systems   69-2480EF—05
22
Follow this diagram if using a 
TrueIAQ (DG115EZIQ)
.
Follow this diagram 
for 
Alternate Interlock 
Wiring with Forced Air 
System
 
The ERV/HRV is interlocked with the forced air system and is used in conjunction with older-style
thermostats where the G and Y terminals are coupled together in the thermostat (fan and cool are 
simultaneously energized).
This wiring method will prevent turning on the cooling system when the ventilator turns on the furnace fan.
NOTE:  Only use this wiring method for systems where G and Y are coupled at the thermostat.
OLDER -STYLE 
THERMOSTAT
FAN (G) & COOL (Y) 
ARE COUPLED
FORCED AIR SYSTEM 
(FURNACE)
24-VOLT
TERMINAL BLOCK
FAN TIMER
OR OTHER 
WALL
CONTROL
POWERED
VENTILATOR
M28992
C
Y
W
G
R
Y
W
G
R
M28993
VENT
VENT
DEHUM
DEHUM
TrueIAQ