C. Water Regulating Valve Adjustment (water-cooled models)
The water regulating valve is factory set, and generally no adjustment is required. However, 
when necessary, adjust the water regulator using the following procedure.
1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure 
gauge to the high-side line of the system.
2) 5 min. after a freeze cycle starts, confirm that the thermometer reads 104°F to 115°F 
(40°C to 46°C). If it does not, rotate the adjustment screw by using a flat blade 
screwdriver until the temperature is in the proper range (rotate counterclockwise to 
raise temperature or clockwise to lower temperature). See Fig. 4. Next, check that the 
reference pressure is in the range indicated in "VIII.A. Specification and Performance 
Data." If it is not in the proper range, verify the refrigerant charge.
3) Check that the condenser drain temperature is stable. 
Fig. 4
Adjustment Screw
CW – Lower
CCW – Higher
Top View