Appendix B. Troubleshooting 
Appendix B.1. Things to check when communications fail. 
 
Check for loose cabling on the third party network 
 
Verify that the correct program is loaded to the CPU 
 
Verify that the correct data types for the tags have been used.   
Appendix B.2. Timeout Errors on S lotServer  
The following remedial action is suggested if timeout errors are experienced: 
 
The PLC is not set to RUN mode - it may still be in PRG mode. Resolve by putting the PLC into RUN mode. 
 
The  IO  image  connection  has  not  been  established  successfully.    The  F  screen  should  show  some  error 
messages  also.  Refer  to  the  Slotserver  Configuration  Manual,  and  insert  the  correct  size  and  RPI  values 
when adding the SlotServer in RSLogix5000. 
Appendix B.3. Data Transfer 
 
It is important that the PLC is set to Run – data is only transferred on Run. 
 
The SlotServer’s Logix connection will transfer data to the PLC regardless of the Node status of the Client 
Nodes.    The  Logix  connection  will  not  be  broken  if  a  Client  Node  goes  offline.    Node  status  can  be 
confirmed by checking the Node Status bits. 
Appendix B.4. ASIC Error on Soft Restart  
If the SlotServer is restarted using Ruinet (!) while the PLC is running, the SlotServer will try to reset the ASIC chip.  
When it finds it is unable to do this it will produce the following Error message and continue to cycle power to the 
SlotServer creating an endless loop. 
 
Under these circumstances it is recommended that the PLC is stopped before the SlotServer is restarted.