SlotServer Start-Up Guide  
 
 
 
 
 
 
 
Page 6 of 14 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
INSTALLATION 
The  SlotServer  plugs  directly  into  the  AB1756  ControlLogix  rack.    Take  note  of  the  slot  number  used  for  the 
SlotServer as this will be needed when configuring the I/O in the RSLogix software.  
2.1 
POWER UP THE DEVICE  
Apply  power  to  the  device.    Refer  to  the  panel  to  ensure  that  the  SlotServer  has  powered  up  successfully.    The 
diagram in Section 1.4 indicates the location of each of these items on the SlotServer panel. 
Scrolling Display 
 
This will Display an OK status when the SlotServer has powered up successfully. 
Card Status 
Indicators:  
 
The Comm and OK lights will indicate green when the SlotServer has powered up 
successfully.  The Sys indicator will indicate green if the external nodes are all 
communicating properly; and red otherwise. 
 
2.2 
INSTALL AND RUN THE UTILITY SOFTWA RE 
 
Plug the supplied USB flash drive into the USB port on a PC/laptop. 
 
Open Index.html to get the menu of options 
 
Run the Install option and follow the installation instructions. 
 
Once installed, the FieldServer Utilities can be located in the Windows Start menu and as a desktop icon.  
2.3 
CONNECT THE PC TO THE SLOTSERVER OVER THE ETHERNET PORT.  
 
If  connecting  through  a  hub/switch,  use  the  supplied  Cat5  UTP  Ethernet  cable  to  connect  between  the 
Ethernet port of the SlotServer and the hub.  Refer to Section 0 for more information. 
 
If it is necessary to connect the PC directly to the SlotServer, a cross-over cable is required (not supplied). 
 
Disable any wireless Ethernet adapters on the PC/Laptop, 
 
It is important that the PC/Laptop is on the same subnet as the SlotServer.  The default IP address on the 
SlotServer Ethernet port is 192.168.2.X.  Refer to the FieldServer Utilities Manual for information on how 
to change the SlotServer’s IP address. 
2.4 
USING THE PING UTILITY TO IDENTIFY THE SLOTSERVER ON THE NETWORK  
 
Select  Start|Programs|FieldServer  Utilities,  browse  to  the  Ping  Utility  and  select  it.    The  display  should 
show 
 
SlotServer Name 
 
IP Address (192.168.2.X) 
 
SlotServer Version 
 
If necessary, refer to Appendix A for troubleshooting tips.