Siemens ASC77.2U 用户手册

下载
页码 5
 
 
Installation Instructions
Document No. 129-420 
December 13, 2004
 
OpenAir™ External Auxiliary Switch 
 
a
b
c
d
e
f
g
EA1
175R1
 
a.  External dual auxiliary switch 
b. Position 
indicator 
c.  GCA/GBB/GIB position adapter 
d.  GMA/GEB position adapter 
e.  3 mm hex key 
f.  Plastic mounting adapter inserts (2) 
g.  Threaded M5 × 25 screws (2) 
 
 
Figure 1.  External Auxiliary Switch Kit Contents. 
Product Description  
The OpenAir External Auxiliary Switch (EAS) provides 
switch functionality for standard model damper actuators 
with easy installation for in-service units. 
Product Number 
ASC77.2U 
Specifications 
Dual Auxiliary Switches 
24 Vac to 250 Vac 
AC 6A resistive 
AC rating 
AC 2 FLA, 12 LRA 
12 Vdc to 30 Vdc 
DC rating 
DC 2A 
Insulation system 
Double insulated 
 
Switch range 
 Switch 
0° to 90° with 5° intervals 
 Recommended 
 
 usage 
0° to 45° 
  Switch B 
0° to 90° with 5° intervals 
 Recommended 
 usage 
45° to 90° 
Switching hysteresis 
2° 
UL listed to UL 873 
cUL certified to Canadian 
Standard C22.2  
No. 24-93 
Electromagnetic 
compatibility 89/336/EEC 
Agency certification 
Low voltage directive 
73/23/EEC 
Conduit Connection 
Threaded 1/2-inch 
NSPT, flex only 
Shipping Weight 
1.1 lb (0.48 kg) 
 
Warning/Caution Notations 
WARNING: 
Personal injury/loss of life 
may occur if you do not follow 
the procedures as specified. 
CAUTION: 
Equipment damage, or loss of 
data may occur if you do not 
follow the procedures as 
specified. 
Required Tools 
Phillips screwdrivers 
No. 2 for screws, No. 1 for adjustment 
Expected Installation Time 
15 minutes 
 Prerequisites 
CAUTION:   
Remove power from in-service damper 
actuator before installing external 
auxiliary switch. 
 
WARNING
Do not open the external auxiliary switch. 
EA1
191R1
ASK75.3U
or
ASK75.1U
ASK75.3U
or
ASK75.1U
 
Figure 2.  NEMA Type 3R Rating Only  
With Use of Weather Shield. 
Item Number 129-420, Rev. 010
 
Page 1 of 5