HP (Hewlett-Packard) 651176-002 用户手册

下载
页码 80
 
Maintenance  46 
1. 
Read and observe the requirements in "Important battery safety information (on page 
)" and "Battery 
care and storage guidelines (on page 
)." 
2. 
Follow the instructions in "UPS battery replacement procedure (on page 
)." 
 
Important battery safety information 
  
 
WARNING:
  The unit contains sealed lead-acid battery modules. To prevent fire or chemical 
burns: 
 
Do not attempt to recharge batteries after removal from the unit. 
 
Do not disassemble, crush, or puncture the batteries. 
 
Do not short the external contacts of the batteries. 
 
Do not immerse the batteries in water. 
 
Do not expose to temperatures higher than 60°C (140°F). 
  
 
  
 
WARNING:
  To prevent personal injury from hazardous energy: 
 
Remove watches, rings, or other metal objects. 
 
Use tools with insulated handles. 
 
Do not place tools or metal parts on top of batteries. 
  
 
  
 
WARNING:
  To prevent personal injury, prepare the area and observe all materials-handling 
procedures when transporting a battery module. Battery modules weigh 20 kg (44.1 lb). 
  
 
  
 
NOTE:
  Replace all battery modules at the same time. 
  
 
Battery care and storage guidelines 
 
Minimize the amount of time the UPS uses battery power by matching the UPS configuration with the 
utility voltage. Refer to "Configuring the UPS (on page 
)."  
 
Keep the area around the UPS clean and dust-free. If the environment is very dusty, clean the outside of 
the UPS regularly with a vacuum cleaner. 
 
Maintain the ambient temperature at 25°C (77°F). 
 
If storing a UPS for an extended period, recharge the batteries every 6 months: 
  
 
CAUTION:
  Because of the short shelf life of the batteries, avoid storing a battery spare as a 
backup. Do not maintain an inventory of spare batteries on site unless a procedure to keep these 
batteries charged while in storage is implemented. 
  
a. 
Connect the UPS to utility power. 
b. 
Allow the UPS to remain in Standby mode. 
c. 
Allow the UPS to charge the batteries for at least 24 hours. 
d. 
Update the battery recharge date label. 
 
Determining when to replace batteries 
When the Battery Fault LED illuminates, batteries might need to be replaced within 30 to 60 days.