Troubleshooting  59 
Overtemperature condition 
Possible cause: The UPS internal temperature is too high, or a fan has failed. 
Action: 
1. 
Power down the UPS ("
" on page 
). 
2. 
Allow the UPS to cool: 
a. 
Clear vents and remove any heat sources. 
b. 
Be sure that the that the airflow around the UPS is not restricted. 
3. 
Wait at least 5 minutes, and then restart the UPS. 
4. 
If the condition persists, contact an HP authorized service representative. 
 
Internal UPS fault condition 
Action: 
1. 
Power down the UPS ("
" on page 
). 
2. 
If the condition persists, contact an HP authorized service representative. 
 
REPO condition 
Action: 
 
If the remote switch is closed, then open the switch to enable power to the output receptacles. 
 
If the condition occurred while reconnecting a disconnected REPO port, then verify the polarity of the 
REPO connector pins. 
For more information about REPO ports, see "Connecting the REPO port (on page 
)." 
 
Site wiring condition 
Action: Contact a qualified electrician to be sure that: 
 
The line and neutral wires are not reversed in the wall outlet. 
 
A ground wire connection does not exist. 
 
Overload condition 
All the load LEDs are illuminated. 
Action: 
1. 
Power down the UPS ("
" on page 
). 
2. 
Remove one or more load devices to reduce the power requirements. 
3. 
Wait at least 5 seconds and restart the UPS. 
4. 
If the condition persists, verify that the load devices are not defective.