4.1 Transport 
 
NOTE: Transport the UPS only in upright position. Check for sufficient floor and elevation loading 
capacity. Move the UPS in its original package to the final destination room. Do not stack other 
package on top. 
 
4.2 Unpacking 
 
Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to 
the pallet. Remove the UPS from the pallet.  
 
BE CAREFUL!
 Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS 
from the pallet! Never try to lift the unit by yourself!  
 
The UPS is equipped with castors, which allow easy displacement of the unit. Please take appropriate 
measures to avoid damage on vulnerable floors. 
 
 
4.3 Package 
Contents 
 
The shipping box contains a LP-U UPS, a CD-ROM, an RS232 cable, a link (5/6kVA models only, see 4.5.3) a 
safety guide and this manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel 
Architecture, right option slot at the rear of the unit) the shipping box also contains a yellow network cable and 
one bus terminator. Inspect the UPS for damage after unpacking. If any damage is present please notify the 
carrier and place of purchase immediately. 
 
 
4.4 Location 
 
Please refer to section 1.3 of ‘IMPORTANT SAFETY INSTRUCTIONS’. 
 
 
4.5 Installation 
 
IMPORTANT
 
Before making any connection and switching on the LP UPS, please check the following conditions: 
 
 
The voltage and frequency of your utility supply is 120/208/230/240 Vac
 
and 50 or 60 Hz; from the 
factory the input and output of the UPS are set to 208 Vac / 60 Hz. 
 
Be sure that the UPS is wired for the present utility voltage. This is indicated on the packaging of the 
UPS, as well as at the I/O terminals. 
 
Overcurrent protection for the AC circuit is to be provided by others. 
 
 CAUTION: 
To reduce risk of fire, connect only to a circuit input/output provided with 
branch circuit overcurrent protection in accordance with the National 
Electrical Code, ANSI / NFPA 70, as indicated below: 
 
UPS model 
Input overcurrent protection 
(Amps) 
Output overcurrent protection 
(Max. Amps) 
Operating input voltage 
120V 208V 240V 120V 
(1 X) 
120V 
(2X) 
208V 240V 
LP 
5-11U 
 
  35 30 40 20 25 20 
LP 5-11U /120V 
60 
 
 
40 
20 
25 
20 
LP 
6-11U 
  40 35 50 25 30 25 
LP 6-11U /120V 
70 
 
 
50 
25 
30 
25 
LP 
8-11U 
  60 45 70 35 40 35 
LP 10-11U 
 
70 
60 
80 
40 
50 
40 
 
Table 1. external input fuse value 