11. 
Configuring alarms 
 
The representation of the color mixing station is now almost complete. Only the alarms are still missing. 
Alarms are generated when an alarm bit occurs (discrete alarms) or when a low or high limit is violated 
(analog alarms). 
The alarm texts contain a description of the alarm source with alarm status or just information about the 
ongoing operation of the plant. 
Alarms are grouped into alarm classes such as Warnings or Errors for operating and fault alarms. 
Operating messages relate to the states of a machine or a process, while fault alarms indicate interrupts 
of a machine or a process and must be acknowledged. 
 
11.1  Analog alarms 
 
The fill levels of the three tanks and the reservoir are to be monitored. 
If a tank or the reservoir is full, a fault alarm should be output. 
 
Double-click HMI alarms in the project window.  
Click the Analog alarms tab. 
 
Enter the message texts and the monitored tags. 
Use the tags of the maximum fill quantities for the limits. 
Enter 2999 as constant value for the limit of the reservoir. 
 
 
 
 
Note 
You can also create multiple alarms for a monitored tag.  
To do so, you only need to specify different limits.