FP-PWM-520 and cFP-PWM-520
Shock and Vibration
These specifications apply only to the cFP-PWM-520. 
NI recommends Compact FieldPoint if your application is 
subject to shock and vibration.
Operating vibration, random
(IEC 60068-2-64).............................. 10–500 Hz, 5 g
rms
Operating vibration, sinusoidal
(IEC 60068-2-6)................................ 10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27).............................. 50 g, 3 ms half sine, 
18 shocks at 6 orientations;
30 g, 11 ms half sine, 
18 shocks at 6 orientations
Hazardous Locations
U.S. (UL) .......................................... Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
AEx nC IIC T4
Canada (C-UL) ................................. Class I, Division 2, 
Groups A, B, C, D, T4;
Class I, Zone 2, 
Ex nC IIC T4
Europe (DEMKO)............................. Ex nC IIC T4
Safety
This product is designed to meet the requirements of the following 
standards of safety for electrical equipment for measurement, 
control, and laboratory use:
IEC 61010-1, EN 61010-1
UL 61010-1, CSA 61010-1
Note
For UL and other safety certifications, refer to the 
product label or visit 
ni.com/certification
, search 
by model number or product line, and click the 
appropriate link in the Certification column.