Mitsubishi Electronics A1SJ71AP23Q 用户手册

下载
页码 158
6
 - 4
6.1 Link Data Send/Receive Processing
6.1.3 Link data handling in the case of a communication error
6
LINK DATA SEND/RECEIVE PROCESSING AND 
PROCESSING TIME
(a) Q series local station (Communication error station)
1) M9250 and M9251 turn ON.
2) The areas, M9241 to M9255 (except for M9250 and M9251) and D9243 to 
D9255 store the data immediately before the communication error.
3) The station holds the data that have been received from other stations and that 
were present immediately before the communication error. 
(b) Master station (Normally operating station)
1) The station No. of the communication error station can be checked in M9237 
and D9228 to D9231. 
2) The mater station holds the data that have been received from the 
communication error station and that were present immediately before the 
communication error. 
(c) Local station (Normally operating station)
1) The station No. of the communication error station can be checked in M9255 
and D9252 to D9255.  
2) The local station holds the data that have been received from the 
communication error station and that were present immediately before the 
communication error.