3  INSTALLATION 
 
NOTE ! 
Strictly observe the ‘UPS Safety Rules’. 
Read carefully the UPS ‘Operating Manual & Installation 
Guide
’ before installing or operating the equipment. 
If any problems are encountered with the installation 
procedure here described, please contact the nearest 
Service Centre before proceeding.
 
 
 
 
3.1  3-PH SNMP/WEB PLUG-IN ADAPTER (P/N 1018959) 
 
NOTE ! 
SitePro customers only 
SitePro units produced before 2003 require an additional 
protective ground connection – refer to APPENDIX A.
 
 
 
3.1.1  Setting the logical address 
The logical address is configured through dip-switch SW1 in the following way: 
 
 
Logical Address  
Dip 1 
Dip 2 
SNMP Card 0 
(1)
 84 
 
(54h) 
ON 
ON 
SNMP Card 1 
85  
(55h) 
ON 
OFF 
SNMP Card 2 
86  
(56h) 
OFF 
ON 
SNMP Card 3 
87  
(57h) 
OFF 
OFF 
(1) Default setup 
 
 
 
Dip-switch SW1 
NOTE:  The logical address is a critical setting when more than one SNMP Card is installed in the same 
UPS system. 
Modifications reserved 
Page 14/24 
ISG_CNT_SNM_BAS_CRD_1GB_V012.doc 
Installation Guide SNMP/Web Adapter