ni.com
Physical
Indicators .......................................... Green POWER and 
READY indicators, 8 green 
output state indicators
Weight
cFP-RLY-421.............................. 130 g (4.5 oz)
Power Requirements
Power from network module ............ 1,700 mW
Isolation Voltage
Maximum isolation voltage .............. 250 V
rms
 
Channel-to-channel isolation ............ No isolation between 
channels
Transient overvoltage........................ 2,300 V
rms
Environmental
FieldPoint modules are intended for indoor use only. For outdoor 
use, they must be mounted inside a sealed enclosure.
Operating temperature ...................... –40 to 60 °C
Storage temperature .......................... –55 to 85 °C 
Humidity ........................................... 10 to 90% RH, 
noncondensing
Maximum altitude............................. 2,000 m; at higher altitudes 
the isolation voltage ratings 
must be lowered
Pollution Degree ............................... 2
Shock and Vibration
Operating vibration, random 
(IEC 60068-2-64).............................. 10–500 Hz, 5 g
rms
Operating vibration, sinusoidal 
(IEC 60068-2-6)................................ 10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27).............................. 50 g, 3 ms half sine, 
18 shocks at 6 orientations;
30 g, 11 ms half sine, 
18 shocks at 6 orientations