NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Test gauge connections are provided on the 
front of the millivolt and electronic gas control 
valve (identified IN for the inlet and OUT for the 
manifold side).  The control valves have a 3/8" 
(10mm) NPT thread inlet and outlet side of the 
valve (refer to Figures 1 and 2).
Propane tanks are at pressures that will cause 
damage to valve components.  Verify that the 
tanks have step down regulators to reduce the 
pressure to safe levels.
Gas Valve Diagrams
See Figure 1 for Millivolt models and Figure 2 
For Electronic Models.
These appliances must not be connected to a 
chimney or flue serving a separate solid fuel 
burning appliance.
Manifold Gas Supply Pressure
(all models)
Fuel #
Low
High
Natural 
Gas
(Lo) 2.2" WC
(0.55 kPa)
(Hi) 3.5" WC
(0.87 kPa)
Propane (Lo) 6.3" WC
(1.57 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Table 3
These appliances must be isolated from the 
gas supply piping system (by closing their 
individual manual shut-off valve) during any 
pressure  testing  of  the  gas  supply  piping 
system  at  test  pressures  equal  to  or  less 
than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off 
valves must be disconnected from the gas 
supply piping system during any pressure 
testing of that system at pressures greater 
than 1/2 psig (3.5 kPa).
Orifice Sizes -  Sea Level to High Altitude
(All Models)
These appliances are tested and approved for 
installation at elevations of 0-4500 feet (0-1372 
meters) above sea level using the standard burner 
orifice sizes (marked with an "*" in Table 4 ).  
For elevations above 4500 feet, contact your gas 
supplier or qualified service technician. 
Deration  -  At  higher  elevations,  the  amount 
of BTU fuel value delivered must be reduced 
by either:
• Using gas that has been derated by the gas 
company.
• By changing the burner orifice to a smaller 
size as regulated by the local authorities having 
jurisdiction and by the (USA) National Fuel Gas 
Code NFPA 54/ANSI Z223.1 - latest edition or, 
in Canada, the CAN/CSA-B149.1 codes - latest 
edition.
Install the appliance according to the regulations 
of the local authorities having jurisdiction and, 
in the USA, the National Fuel Gas Code NFPA 
54 / ANSI Z223.1 - latest edition or, in Canada, 
the CAN/CSA-B149.1 - latest edition.
Flame breadth, height and width will diminish 
4% for every 1,000 feet of altitude.
REQUIREMENTS  FOR  THE  COMMON-
WEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in 
the US state of Massachusetts if the following 
additional requirements are met:
•  Install  this  appliance  in  accordance  with 
Massachusetts Rules and Regulations 248 
C.M.R. 
•  Installation and repair must be done by a 
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
•  The flexible gas line connector used shall 
not exceed 36 inches (92 centimeters) in 
length.
•  The individual manual shut-off must be a 
T-handle type valve.
Massachusetts Horizontal Vent Requirements 
In the Commonwealth of Massachusetts, hori-
zontal terminations installed less than seven 
(7) feet above the finished grade must comply 
with the following additional requirements:
•  A  hard  wired  carbon  monoxide  detector 
with an alarm and battery back-up must be 
installed  on  the  floor  level  where  the  gas 
fireplace is installed.  The carbon monoxide 
detector must comply with NFPA 720, be 
ANSI/UL 2034 listed and be ISA certified.
•  A metal or plastic identification plate must 
be permanently mounted to the exterior of 
the building at a minimum height of eight (8) 
feet above grade and be directly in line with 
the horizontal termination.  The sign must 
read, in print size no less than one-half (1/2) 
inch in size, GAS VENT DIRECTLY BELOW.  
KEEP CLEAR OF ALL OBSTRUCTIONS.
NEW YORK CITY, NEW YORK (MEA)
Installation  of  these  fireplaces  are  approved 
for installation in New York City in the US state 
of New York.
Inlet Gas Supply Pressure 
(all models)
Fuel #
Minimum
Maximum
Natural Gas
4.5" WC
(1.12 kPa)
10.5" WC
(2.61 kPa)
Propane
11.0" WC
(2.74 kPa)
13.0" WC
(3.23 kPa)
Table 2
Gas Pressure - All Models
Tables 2 and 3
 show the appliances' inlet and 
manifold gas pressure requirements:
Figure 2
Honeywell Electronic
 Gas Valve
ON/OFF Switch
Electronic
Gas Control
Valve
Inlet
Pressure
Port
Manifold Pressure Port
OFF
IN
PSI
ON
CONTROL
IGNITER
H I
LO
W
HT
PT
HT
PT
PILO
T
PI
LO
T
ON
it
OFF
IN
OUT
HI/LO Variable
Flame Height
Adjustment
Figure 1 - 
SIT Millivolt  Gas Valve
Manifold Pressure Tap
Inlet Pressure Tap
Pilot Adjustment
Screw
Main Gas Control Knob
OFF/PILOT/ON
Burner Orifice Sizes (all models)
Elevation
Feet (meters)
Natural
Gas
drill size (inches)
Propane
Gas
drill size (inches)
0-4500
(0-1372)
(0.125") 
*
21L81 •
#41 (0.096")
*
21L82 •
Table 4           
* Standard size installed at factory
                                        •  Part /Cat. Number