Vanguard Heating Gas Log Heater 用户手册

下载
页码 36
13
103515
INSTALLING
Continued
Floor Clearances
A. If installing appliance on the floor level, you must maintain the minimum
distance of 14" to combustibles (see Figure 8).
Figure 8 - Minimum Fireplace Clearances If Installed at Floor Level
B. If combustible materials are less than 14" to the fireplace, you must install
appliance at least 5" above the combustible flooring (see Figure 9).
Figure 9 - Minimum Fireplace Clearances Above Combustible Flooring
If your installation does not meet the above minimum clearances, you must:
• operate the logs only with the flue damper open, OR
• raise the mantel to an acceptable height, OR
• remove the mantel.
Figure 7 - Minimum Mantel Clearances When Using Hood
Continued
Minimum Non-
Combustible 
Material 
8"
Min.
12"
15"
18"
All minimum 
distances are
in inches
Log Sets
18", 24", and 
30" Models
20"
1
/2
"
6"
8"
10"
12"
Distances to 
Underside of
Mantel 
Hood
(GA6050, GA6052)
Top of Fireplace
Opening
Underside of
Mantel Shelf
Mantel Shelf
14"
Min.
Combustible 
Material 
Non-Combustible Material 
Hearth
5"
Min.
Combustible 
Material