Instruction 3015-4286 
DIAGNOS
 – Enters the diagnostic function. Press the Up Arrow 
Keypad button to toggle between the monitor’s two diagnostic screens. 
 
 
 
 
GASTYPE
 – Ammonia monitors do not have a library of other gases to 
choose from, therefore R717 is the only gas type listed. Press QUIT to 
return to the previous screen. 
LEAKLVL
 – Sets the Leak Alarm level, adjustable from 1 to 300 ppm. 
Factory default is 100 ppm. Note that the Leak Alarm level cannot be set 
higher than either the Spill or Evacuate Alarm levels. Use the Keypad to 
set the desired Leak Alarm level, and then press ENTER to save that 
level and return to the previous screen. 
SPILLLVL
 – Sets the Spill Alarm level, adjustable from no lower than 
the Leak Alarm level to a maximum value of 500 ppm, but not higher 
than the Evacuate Alarm level. Factory default is 300 ppm. Use the 
Keypad to set the desired Spill Alarm level, and then press ENTER to 
save that level and return to the previous screen. 
EVACLVL
 – Sets the Evacuate Alarm level, adjustable from no lower 
than the Spill Alarm level to 9999 ppm. Factory default is 500 ppm. Use 
the Keypad to set the desired spill level alarm level, and then press 
ENTER to save that level and return to the previous screen. 
LOG INT
 – Sets the interval at which measurements are logged to 
memory from 1 to 9999 minutes. Factory default is 10 minutes. Note that 
the logged measurements can be viewed using the PPM LOG function. 
Use the Keypad to enter the desired value, and then press ENTER to 
save that value and return to the previous screen. 
LOOP
 – Adjusts the loop factor of the 4–20 mA current loop. Factory 
default is 0.016 mA per ppm, which provides an output range of 0 ppm 
(4 mA) to 1,000 ppm (20 mA). Use the Keypad to set the desired loop 
factor, and then press ENTER to save that value and return to the 
previous screen. 
To facilitate loop zero and span checking, note that when the LOOP 
function is selected the loop output is set to 20 mA, and upon exiting this 
function the loop output is set to 4 mA. 
AUDALRM
 – 
Allows the monitor’s internal audible alarm to be 
associated with any function of the monitoring system. Factory default is 
OFF. Use the Keypad to select the desired audible alarm function, and 
then press ENTER to save that value and return to the previous screen.
  
Audible Alarm Settings: OFF, ANY ALARM, SYSTEM FAULT, LEAK ALARM, 
SPILL ALARM, EVAC ALARM, MONITOR STOPPED 
NOTE: 
MONITOR STOPPED indicates there is a critical system fault, and the 
monitor is no longer functioning correctly.  
 
 
LOG INTERVAL IS
    0010 min
EDIT LOOP FACTOR
 0.016 ma/PPM
AUDIBLE ALARM IS
 OFF 
4.26500v  <0000>
24.5cD  14.00psi
   0.4ppm  0.00
0.00002au 4.260v
SELECT GAS TYPE
   R717 
EDIT EVAC LEVEL
    0500 PPM
EDIT LEAK LEVEL
    0100 PPM
EDIT SPILL LEVEL
    0300 PPM