9. CONFIGURING THE PID
Use this page to configure the PID parameters for both the heating and cooling loops in a Stryker VAV device.
To set PID:
9.1 Fields
Flow Tracking Offset
Represents the flow tracking offset value used when FlowType is configured as FlowTracking. This 
offset is added to the value of nviFlowTrack to determine the flow setpoint.
Terminal load calculation Enables you to perform the terminal load calculation. You have the option to select 0 or 1 in the 
Terminal load calculation field.
Select 0 to use the conventional zone terminal load calculation.
The conventional zone terminal load calculation uses the PID output of heating and cooling 
controls.  When the controller is switched to the heating mode, the Terminal load is ? 0. 
Select 1 to use the CZS zone terminal load calculation.
The CZS zone terminal load calculation uses the proportional output of heating and cooling 
controls.  When the controller is switched to the heating mode, the Terminal Load continues to 
report both heating and cooling demand.  The terminal load absolute value is truncated at 100%.
Table 9. Configuring the Control Parameter Fields. (Continued)
Name
Definition
Step
Action
1
From the left pane of the 
VAV Configuration Wizard, select PID.
2
Enter information in the available fields.
3
Click 
Next to display the Accessory Loops page.
4
Click 
Undo All to revert to the last saved settings.
5
Click 
Finish to save settings to station.
Table 10. PID Names.
Name
Definition
Cooling Throttling 
Range
Value must be between 2 to 30 DDF.
Cooling Integral Time
Value must be between 0 to 9000 sec.
Cooling Derivative 
Time
Value must be between 0 to 9000 sec.
Heating Throttling 
Range
Value must be configured based on reheat configuration. 
Reheat Type
TR (DegF)
modulating
5
1 stage
3
2 stage
4
3 stage
7
4 stage
8