ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills 
or  ducts. You  must  provide  two  permanent 
openings: one within 12" (30.5 cm) of the ceil-
AIR FOR COMBUSTION AND VENTILATION
Continued
Figure 2 - Ventilation Air from Inside 
Building
Figure 3 - Ventilation Air from Outdoors
ing and one within 12" (30.5 cm) of the floor. 
Connect these items directly to the outdoors 
or spaces open to the outdoors. These spaces 
include attics and crawl spaces. Follow the Na-
tional Fuel Gas Code, ANSI Z223.1/NFPA 54, 
Air for Combustion and Ventilation for required 
size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet 
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the 
attic will activate the power vent.
INSTALLATION
NOTICE: This heater is intended 
for  use  as  supplemental  heat. 
Use this heater along with your 
primary heating system. Do not 
install  this  heater  as  your  pri-
mary heat source. If you have a 
central heating system, you may 
run system’s circulating blower 
while using heater. This will help 
circulate the heat throughout the 
house. In the event of a power 
outage, you can use this heater 
as your primary heat source.
 WARNING: A qualified ser-
vice person must install heater. 
Follow all local codes.
 WARNING: This appliance is 
equipped for either natural gas or 
propane/LP gas but not both. Gas 
type is indicated on the rating plate. 
Field conversion is not permitted.
CHECK GAS TYPE
Use only the correct gas type (natural 
or propane/LP) for your unit. If your gas 
supply is not correct, do not install heater. 
Call dealer where you bought heater for 
proper type heater. 
INSTALLATION ITEMS
Before installing heater, make sure you have 
the items listed below.
•   for  propane/LP  gas,  external  regulator 
(supplied by installer)
•   piping (check local codes)
•  sealant (resistant to propane/LP gas)
•   equipment shutoff valve *
•  ground joint union
•   sediment trap
•   tee joint
•   pipe wrench
•   for natural gas, test gauge connection*
•   hardware packet (included)
- wall anchor (4) 095112-02
- red key (1) 095116-01
- pan head screw, black (4) 097403-02
- nylon spacer (2) 099064-02
- clip (1) 099123-01
- Phillips head screw, silver (4) 100159-02
* An equipment shutoff valve with 1/8" NPT tap 
is an acceptable alternative to test gauge con-
nection. The optional equipment shutoff valve 
can be purchased from your dealer. 
Or  
Remove  
Door into  
Adjoining  
Room,  
Option 3 
Ventilation Grills  
Into Adjoining Room, 
Option 2 
12" 
12" 
Ventilation
Grills into
Adjoining
Room, 
Option 1
Outlet 
Air 
Ventilated 
Attic  
Outlet 
Air 
Inlet 
Air 
Inlet Air 
Ventilated  
Crawl Space 
To  
Crawl 
Space 
To Attic