Installation
 
5.3.3 Thermocouple Output 
If  you  are  using  a  J‐  or  K‐  thermocouple  you  must  install  a 
compensation  cable.  The  cable  is  available  as  an  accessory 
(XXXCI1CB25  for  Type  J,  XXXCI2CB25  for  Type  K)  with  a  cable 
length of 7.5 m (24.6 ft.) 
Connect the wires according to the following table: 
J-Thermocouple 
Power Supply 
white 
– 
red-white 
red-yellow 
– 
yellow 
Table 1: Wiring the Thermocouple J Compensation Cable 
K-Thermocouple 
Power Supply 
yellow 
– 
red-yellow  
red-white 
– 
white 
Table 2: Wiring the Thermocouple K Compensation Cable 
 
Power + 
red-yellow 
Power – 
yellow 
TC J – 
red-white
TC J + 
white 
Figure 12: Wiring the Thermocouple J Compensation Cable 
22 