5
cFP-CB-1/2/3/4
2. Verify that there are no cuts in the wire insulation that can 
cause a safety hazard.
3. Strip 6 mm (0.24 in.) of insulation from the ends of the wires.
4. Insert the entire stripped ends of the wires into the appropriate 
screw terminals. Do not allow any bare wire to show outside 
the screw terminals.
5. Using a 1/8 in. flathead screwdriver, tighten the screw 
terminals to 0.5–0.6 N
⋅ m (4.4–5.3 lb ⋅ in.) of torque.
Wiring to the cFP-CB-2
You need a flathead screwdriver with a blade smaller than 
2.3 × 1.0 mm (0.09 × 0.04 in.) to connect wires to the detachable 
spring-terminal connector. Complete the following steps:
1. Verify that there are no cuts in the wire insulation that can 
cause a safety hazard.
2. Strip 7 mm (0.28 in.) of insulation from the ends of the wires.
3. Insert the screwdriver into a spring clamp activation slot.
4. Insert the entire stripped end of the wire into the corresponding 
spring terminal. Do not allow any bare wire to show outside the 
terminal.
5. Remove the screwdriver to clamp the wire into the terminal.
Figure 6.  Connecting a Wire to the Spring-Terminal Connector of the cFP-CB-2
6. When the wiring is complete, insert the connector into the 
cFP-CB-2.