National Instruments 370578B-01 用户手册

下载
页码 39
Chapter 2
Installation and Configuration
2-8
ni.com
that you deleted the last interface, because all the remaining interface 
numbers are decreased by one automatically.
To reinstall the interface, refer to the 
section and the 
 section.
Importing Device Descriptions
The device description files contain information about the types of blocks 
and parameters supported by your Fieldbus device, along with online help 
describing the uses of given parameters. If your Fieldbus device uses 
manufacturer-specific device description files, you must import the device 
description files (shipped with the device, or available from the device 
manufacturer). To do so, complete the following steps:
1.
Insert the device description disk or CD (if supplied by your Fieldbus 
device manufacturer) into the disk drive of the host computer.
2.
Select Start»Programs»National Instruments»NI-FBUS» 
Interface Configuration Utility to
 run the Interface Configuration 
Utility.
3.
Click Import DD/CFF. The Import DD/CFF dialog box opens.
4.
Click Browse, browse to the 
.ffo
 device description file path, and 
click Open. Typically, the device description for your Fieldbus device 
is supplied on a disk from the manufacturer. For each device, there are 
two device description files, one that ends in 
.ffo
 and one that ends 
in 
.sym
. Select the 
.ffo
 file, and the corresponding 
.sym
 file will 
be imported automatically. The file name will be in the form 
Digit Digit Digit Digit.ffo
 (for example, 
0101.ffo
).
Table 2-1.  Board Renumbering
Original Address
Address after Deleting Board1
Board0
Board0
Board1
(deleted)
Board2
Board1
Board3
Board2