Honeywell 301C 用户手册

下载
页码 107
Honeywell 301C User Manual 
Base Objects  
 
 
76 
 
Data Type
Required
1
Storage
Type
2
BACnet 
Writeable?
Value
object_identifier
R
C
N
46344 (or 0xB508) for Relay #1 up to 
46347 (or 0xB50B) for Relay #4
object_type
enumerated
R
C
N
binary_output (4)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"device_object_name.relX", where 
device_object_name 
is programmed on the 
LUI and defaults to "VA301C:1" and  is 
relay number (1 to 4).  Thus the default 
object_name for Relay #4 will be 
"VA301C:1.rel4"
out_of_service
boolean
R
C
N
FALSE
polarity
enumerated
R
C
N
always Normal (0)
present_value
enumerated
R
R
Only 
Rly1&2. Not 
Rly 3or4.
True state of the relays.  These take the 
value of the highest-priority BACnet 
command.  If no BACnet command, this 
takes the value of the associated event.
priority_array
R
R
N
last value written
reliability
enumerated
0
C
N
no_fault_detected (0)
relinquish_default
R
C
N
not meaningful
active_text
character string
O
C
N
"ON"
inactive_text
character string
O
C
N
"OFF"
status_flags
in_alarm
boolean
R
C
N
always "false" (0)
fault
boolean
R
C
N
always "false" (0)
overridden
boolean
R
R
N
always "false" (0)
out_of_service boolean
R
R
N
always "false" (0)
object_identifier
R
C
N
46360 (or 0xB518)
object_type
enumerated
R
C
N
binary_output (4)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"device_object_name.buzz", where 
device_object_name 
is programmed on the 
LUI and defaults to "VA301C:1" .  Thus the 
default object_name will be 
"VA301C:1.buzz"
out_of_service
boolean
R
C
N
FALSE
polarity
enumerated
R
C
N
always Normal (0)
present_value
enumerated
R
R
Y
True state of the buzzer.  This takes the 
value of the highest-priority BACnet 
command.  If no BACnet command, this 
takes the value of the associated event.
priority_array
R
R
N
last value written
reliability
enumerated
0
C
N
no_fault_detected (0)
relinquish_default
R
C
N
not meaningful
status_flags
in_alarm
boolean
R
C
N
always "false" (0)
fault
boolean
R
C
N
always "false" (0)
overridden
boolean
R
C
N
always "false" (0)
out_of_service boolean
R
C
N
always "false" (0)
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
bu
zz
re
l1
 to
 re
l4
Bi
na
ry
 O
ut
pu
ts
Group
Property