XNX and XCD continued
 
 
 
Group
Property
Data Type
Required
1
Storage 
Type
2
BACnet 
Writeable?
Value
object_identifier
R
N
N
Modbus address * 256 + 2.  For example an 
XNX at Modbus address 010 will appear as 
2562 or 0x0A02.
object_type
enumerated
R
C
N
analog_value (2)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"SSS GGGG   AdAAA.AlarmA" where SSS is 
the sensor type, GGGG is the gas name and 
AAA is the Modbus address.  Values for gas 
name include "CO" and "COMB".  Gas 
names are truncated to 4 characters.  
Values for sensor type are "XNX" or "XCD" 
For example, an XNX at address 10 with a 
Methane sensor will populate this object 
name with "XNX      Meth  Ad010.AlarmA"
out_of_service
boolean
R
C
N
FALSE
present_value
real
R
N
N
Alarm1 threshold copied from sensor 
through the 301C.  This may only be 
modified on the sensor.
reliability
enumerated
O
C
N
always false (0)
status_flags
in_alarm
boolean
R
C
N
always false (0)
fault
boolean
R
C
N
always false (0)
overridden
boolean
R
C
N
always false (0)
out_of_service boolean
R
C
N
always false (0)
units
enumerated
R
C
N
96 (ppm) or
98 (percent) or
95 (no_units)
object_identifier
R
N
N
Modbus address * 256 + 4.  For example an 
XCD at Modbus address 011 will appear as 
2820 or 0x0B04.
object_type
enumerated
R
C
N
analog_value (2)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"SSS GGGG   AdAAA.AlarmB" where SSS is 
the sensor type, GGGG is the gas name and 
AAA is the Modbus address.   Gas names 
are truncated to 4 characters.  Values for 
sensor type are "XNX" or "XCD" For 
example, an XCD at address 11 with an H2S 
sensor will populate this object name with 
"XCD      H2S   Ad011.AlarmB"
out_of_service
boolean
R
C
N
FALSE
present_value
real
R
N
N
Alarm2 threshold copied from sensor 
through the 301C.  This may only be 
modified on the sensor.
reliability
enumerated
O
C
N
no_fault_detected (0)
status_flags
in_alarm
boolean
R
C
N
always false (0)
fault
boolean
R
C
N
always false (0)
overridden
boolean
R
C
N
always false (0)
out_of_service boolean
R
C
N
always false (0)
units
enumerated
R
C
N
96 (ppm) or
98 (percent) or
95 (no_units)
An
alo
g V
alu
es
Ala
rm
A
Ala
rm
B
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
 
   
  
 
   
   