You must connect the protective earth (PE) ground terminal on 
the cFP-BP-x or cFP-180x backplane to the system safety 
ground. The backplane PE ground terminal has the following 
symbol stamped beside it: 
. Connect the backplane PE 
ground terminal to the system safety ground using 14 AWG 
(1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw 
shipped with the backplane to secure the ring lug to the 
backplane PE ground terminal.
As with any hazardous voltage wiring, make sure that all 
wiring and connections meet applicable electrical codes and 
commonsense practices. Mount the backplane in an area, 
position, or cabinet that prevents accidental or unauthorized 
access to wiring that carries hazardous voltages.
The isolation of the cFP-CB-x is certified as double-insulated 
for working voltages of up to 250 V
rms
.
Operate the cFP-CB-x only at or below Pollution Degree 2. 
Pollution Degree 2 means that only nonconductive pollution 
occurs in most cases. Occasionally, however, a temporary 
conductivity caused by condensation must be expected.
Do not operate FieldPoint products in an explosive atmosphere 
or where there may be flammable gases or fumes. If you need 
to operate FieldPoint products in such an environment, the 
FieldPoint products must be in a suitably rated enclosure.
Operate the cFP-CB-x at or below Measurement Category II. 
Measurement Category II is for measurements performed on 
circuits directly connected to the electrical distribution system. 
This category refers to local-level distribution, such as that 
provided by a standard wall outlet.