用户手册目录FR-F700P INSTRUCTION MANUAL (Applied)1This section is specifically about safety matters2CONTENTS41 OUTLINE121.1 Product checking and parts identification131.2 Inverter and peripheral devices141.2.1 Peripheral devices151.3 Method of removal and reinstallation of the front cover171.4 Installation of the inverter and enclosure design191.4.1 Inverter installation environment191.4.2 Cooling system for inverter enclosure211.4.3 Inverter placement212 WIRING242.1 Wiring252.1.1 Terminal connection diagram252.1.2 EMC filter262.2 Main circuit terminal specifications272.2.1 Specification of main circuit terminal272.2.2 Terminal arrangement of the main circuit terminal, power supply and the motor wiring272.2.3 Cables and wiring length312.2.4 When connecting the control circuit and the main circuit separately to the power supply352.3 Control circuit specifications372.3.1 Control circuit terminals372.3.2 Changing the control logic402.3.3 Control circuit terminal layout422.3.4 Wiring instructions422.3.5 Mounting the operation panel (FR-DU07) on the enclosure surface432.3.6 RS-485 terminal block442.3.7 Communication operation442.4 Connection of stand-alone option units452.4.1 Connection of the brake unit (FR-BU2)452.4.2 Connection of the brake unit (FR-BU/MT-BU5)472.4.3 Connection of the brake unit (BU type)492.4.4 Connection of the high power factor converter (FR-HC/MT-HC)492.4.5 Connection of the power regeneration common converter (FR-CV) (55K or lower)512.4.6 Connection of the power regeneration converter (MT-RC) (75K or higher)522.4.7 Connection of the power factor improving DC reactor (FR-HEL)533 PRECAUTIONS FOR USE OF THE INVERTER543.1 EMC and leakage currents553.1.1 Leakage currents and countermeasures553.1.2 EMC measures573.1.3 Power supply harmonics593.1.4 Harmonic suppression guideline603.2 Installation of a reactor633.3 Power-OFF and magnetic contactor (MC)633.4 Inverter-driven 400V class motor643.5 Precautions for use of the inverter653.6 Failsafe of the system which uses the inverter674 PARAMETERS704.1 Operation panel (FR-DU07)714.1.1 Component of the operation panel (FR-DU07)714.1.2 Basic operation (factory setting)724.1.3 Easy operation mode setting (easy setting mode)734.1.4 Changing the parameter setting value744.1.5 Displaying the set frequency744.2 Parameter list754.2.1 Parameter list75Parameters according to purposes854.3 IPM motor control <IPM>884.3.1 Setting procedure of IPM motor control <IPM>884.3.2 Initializing the parameters required to drive an IPM motor (Pr.998) <IPM>914.3.3 IPM motor test operation (Pr.800) <IPM>934.3.4 Adjusting the speed control gain (Pr.820, Pr.821) <IPM>954.4 Adjustment of the output torque (current) of the motor984.4.1 Manual torque boost (Pr. 0, Pr. 46) <V/F>984.4.2 Simple magnetic flux vector control (Pr.80, Pr.90) <S MFVC>1004.4.3 Slip compensation (Pr. 245 to Pr. 247) <V/F><S MFVC>1014.4.4 Stall prevention operation (Pr. 22, Pr. 23, Pr. 48, Pr. 49, Pr. 66, Pr. 148, Pr. 149, Pr. 154, Pr. 156, Pr. 157)1024.5 Limiting the output frequency1074.5.1 Maximum/minimum frequency (Pr. 1, Pr. 2, Pr. 18)1074.5.2 Avoiding mechanical resonance points (Frequency jump) (Pr. 31 to Pr. 36)1084.6 V/F pattern1094.6.1 Base frequency, voltage (Pr. 3, Pr. 19, Pr. 47) <V/F><S MFVC>1094.6.2 Load pattern selection (Pr. 14) <V/F>1114.6.3 Adjustable 5 points V/F (Pr. 71, Pr. 100 to Pr. 109) <V/F>1124.7 Frequency setting by external terminals1134.7.1 Multi-speed setting operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)1134.7.2 Jog operation (Pr. 15, Pr. 16)1154.7.3 Input compensation of multi-speed and remote setting (Pr. 28)1174.7.4 Remote setting function (Pr. 59)1174.8 Setting of acceleration/deceleration time and acceleration/deceleration pattern1204.8.1 Setting of the acceleration and deceleration time (Pr.7, Pr.8, Pr.20, Pr.21, Pr.44, Pr.45, Pr.147, Pr.791, Pr.792)1204.8.2 Starting frequency and start-time hold function (Pr.13, Pr.571) <V/F><S MFVC>1244.8.3 Minimum motor rotation frequency (Pr.13) <IPM>1254.8.4 Acceleration/deceleration pattern (Pr.29, Pr.140 to Pr.143)1264.9 Selection and protection of a motor1284.9.1 Motor protection from overheat (Electronic thermal relay function) (Pr. 9, Pr. 51)1284.9.2 Applied motor (Pr. 71)1334.10 Motor brake and stop operation1344.10.1 DC injection brake of general-purpose motor control (Pr. 10 to Pr. 12) <V/F><S MFVC>1344.10.2 DC injection brake of IPM motor control (Pr.10, Pr.11) <IPM>1354.10.3 Selection of a regenerative brake and DC feeding (Pr. 30, Pr. 70)1364.10.4 Stop selection (Pr. 250)1414.10.5 Output stop function (Pr.522)1424.11 Function assignment of external terminal and control1444.11.1 Input terminal function selection (Pr. 178 to Pr. 189)1444.11.2 Inverter output shutoff signal (MRS signal, Pr. 17)1474.11.3 Condition selection of function validity by the second function selection signal (RT) (RT signal, Pr. 155)1484.11.4 Start signal selection (STF, STR, STOP signal, Pr. 250)1494.11.5 Output terminal function selection (Pr. 190 to Pr. 196)1514.11.6 Detection of output frequency (SU, FU, FU2 signal, Pr. 41 to Pr. 43, Pr. 50, Pr. 870)1554.11.7 Output current detection function (Y12 signal, Y13 signal, Pr. 150 to Pr. 153, Pr. 166, Pr. 167)1574.11.8 Remote output function (REM signal, Pr. 495 to Pr. 497)1594.11.9 Pulse train output of output power (Y79 signal, Pr. 799)1604.12 Monitor display and monitor output signal1614.12.1 Speed display and speed setting (Pr. 37, Pr. 144, Pr. 505)1614.12.2 DU/PU monitor display selection (Pr. 52, Pr. 54, Pr. 158, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891)1634.12.3 FM, AM terminal function selection (Pr.55, Pr.56, Pr.867)1684.12.4 Terminal FM, AM calibration (Calibration parameter C0 (Pr. 900), C1 (Pr. 901))1704.12.5 How to calibrate the terminal FM when using the operation panel (FR-DU07)1724.13 Operation selection at power failure and instantaneous power failure1734.13.1 Automatic restart after instantaneous power failure/flying start under general- purpose motor control (Pr. 57, Pr. 58, Pr. 162 to Pr. 165, Pr. 299, Pr. 611) <V/F><S MFVC>1734.13.2 Automatic restart after instantaneous power failure/flying start under IPM motor control (Pr. 57, Pr. 162, Pr. 611) <IPM>1774.13.3 Power failure signal (Y67 signal)1794.13.4 Power failure-time deceleration-to-stop function (Pr. 261 to Pr. 266 )1804.14 Operation setting at fault occurrence1834.14.1 Retry function (Pr. 65, Pr. 67 to Pr. 69)1834.14.2 Fault code output selection (Pr.76)1854.14.3 Input/output phase loss protection selection (Pr. 251, Pr. 872)1864.15 Energy saving operation and energy saving monitor1874.15.1 Energy saving control and Optimum excitation control (Pr. 60) <V/F>1874.15.2 Energy saving monitor (Pr. 891 to Pr. 899)1884.16 Motor noise, EMI measures, mechanical resonance1934.16.1 Carrier frequency and Soft-PWM selection under general-purpose motor control (Pr. 72, Pr. 240, Pr. 260) <V/F><S MFVC>1934.16.2 Carrier frequency and Soft-PWM selection under IPM motor control (Pr.72, Pr.240, Pr.260) <IPM>1944.16.3 Speed smoothing control (Pr. 653, Pr. 654) <V/F><S MFVC>1954.17 Frequency setting by analog input (terminal 1, 2, 4)1964.17.1 Analog input selection (Pr. 73, Pr. 267)1964.17.2 Setting the frequency by analog input (voltage input)2004.17.3 Analog input compensation (Pr. 73, Pr. 242, Pr. 243, Pr. 252, Pr. 253)2024.17.4 Response level of analog input and noise elimination (Pr. 74)2034.17.5 Bias and gain of frequency setting voltage (current) (Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) to C7(Pr. 905))2044.17.6 Frequency setting signal (current) bias/gain adjustment method2064.18 Misoperation prevention and parameter setting restriction2094.18.1 Reset selection/disconnected PU detection/PU stop selection (Pr. 75)2094.18.2 Parameter write selection (Pr. 77)2114.18.3 Reverse rotation prevention selection (Pr. 78)2124.18.4 Display of applied parameters and user group function (Pr. 160, Pr. 172 to Pr. 174)2124.18.5 Password function (Pr. 296, Pr. 297)2144.19 Selection of operation mode and operation location2174.19.1 Operation mode selection (Pr. 79)2174.19.2 Setting the set frequency to operate (example: performing operation at 30Hz)2254.19.3 Setting the frequency by the operation panel (Pr. 79 = 3)2264.19.4 Setting the frequency by analog input (voltage input)2284.19.5 Operation mode at power-ON (Pr. 79, Pr. 340)2294.19.6 Start command source and speed command source during communication operation (Pr. 338, Pr. 339, Pr. 550, Pr. 551)2304.20 Communication operation and setting2354.20.1 Wiring and configuration of PU connector2354.20.2 Wiring and configuration of RS-485 terminals2374.20.3 Initial settings and specifications of RS-485 communication (Pr. 117 to Pr. 124, Pr. 331 to Pr. 337, Pr. 341, Pr. 549)2404.20.4 Communication EEPROM write selection (Pr. 342)2414.20.5 Operation selection at communication error (Pr.502, Pr.779)2424.20.6 Mitsubishi inverter protocol (computer link communication)2454.20.7 Modbus-RTU communication specifications (Pr. 331, Pr. 332, Pr. 334, Pr. 343, Pr. 539, Pr. 549, Pr. 779)2584.21 Special operation and frequency control2724.21.1 PID control (Pr. 127 to Pr. 134, Pr. 241, Pr. 553, Pr. 554, Pr. 575 to Pr. 577, C42 (Pr. 934) to C45 (Pr. 935))2724.21.2 Bypass-inverter switchover function (pr. 57, Pr. 58, Pr. 135 to Pr. 139, Pr. 159) <V/F><S MFVC>2854.21.3 Regeneration avoidance function (Pr. 665, Pr. 882 to Pr. 886)2904.22 Useful functions2924.22.1 Cooling fan operation selection (Pr. 244)2924.22.2 Display of the life of the inverter parts (Pr. 255 to Pr .259)2934.22.3 Maintenance timer alarm (Pr. 503, Pr. 504)2964.22.4 Current average value monitor signal (Pr. 555 to Pr. 557)2974.22.5 Free parameter (Pr. 888, Pr. 889)2994.22.6 Initiating a fault (Pr.997)3004.22.7 Setting multiple parameters as a batch (Pr.999)3014.23 Setting from the parameter unit, operation panel3064.23.1 PU display language selection (Pr. 145)3064.23.2 Setting dial potentiometer mode/key lock selection (Pr. 161)3064.23.3 Buzzer control (Pr. 990)3094.23.4 PU contrast adjustment (Pr. 991)3094.24 Parameter clear3104.25 All parameter clear3114.26 Parameter copy and parameter verification3124.26.1 Parameter copy3124.26.2 Parameter verification3134.27 Initial value change list3144.28 Check and clear of the faults history3155 PROTECTIVE FUNCTIONS3185.1 Reset method of protective function3195.2 List of fault or alarm display3205.3 Causes and corrective actions3215.4 Correspondences between digital and actual characters3335.5 Check first when you have a trouble3345.5.1 Motor does not start3345.5.2 Motor or machine is making abnormal acoustic noise3365.5.3 Inverter generates abnormal noise3365.5.4 Motor generates heat abnormally3365.5.5 Motor rotates in the opposite direction3375.5.6 Speed greatly differs from the setting3375.5.7 Acceleration/deceleration is not smooth3375.5.8 Speed varies during operation3385.5.9 Operation mode is not changed properly3385.5.10 Operation panel (FR-DU07) display is not operating3395.5.11 Motor current is too large3395.5.12 Speed does not accelerate3405.5.13 Unable to write parameter setting3405.5.14 Power lamp is not lit3406 PRECAUTIONS FOR MAINTENANCE AND INSPECTION3426.1 Inspection item3436.1.1 Daily inspection3436.1.2 Periodic inspection3436.1.3 Daily and periodic inspection3446.1.4 Display of the life of the inverter parts3456.1.5 Checking the inverter and converter modules3456.1.6 Cleaning3466.1.7 Replacement of parts3466.1.8 Inverter replacement3506.2 Measurement of main circuit voltages, currents and powers3516.2.1 Measurement of powers3536.2.2 Measurement of voltages and use of PT3536.2.3 Measurement of currents3546.2.4 Use of CT and transducer3546.2.5 Measurement of inverter input power factor3546.2.6 Measurement of converter output voltage (across terminals P/+ and N/-)3556.2.7 Measurement of inverter output frequency3556.2.8 Insulation resistance test using megger3556.2.9 Pressure test3557 SPECIFICATIONS3567.1 Rating3577.2 Common specifications3597.3 Outline dimension drawings3617.3.1 Inverter outline dimension drawings3617.4 Specification of premium high-efficiency IPM motor [MM-EFS (1500r/min) series]3707.5 Specification of high-efficiency IPM motor [MM-EF (1800r/min) series]3717.6 Heatsink protrusion attachment procedure3727.6.1 When using a heatsink protrusion attachment (FR-A7CN)3727.6.2 Protrusion of heatsink of the FR-F740P-185K or higher372APPENDICES374Appendix 1 For customers who are replacing the conventional model with this inverter375Appendix 1-1 Replacement of the FR-F500 series375Appendix 1-2 Replacement of the FR-A100 <EXCELENT> series376Appendix 2 Options and products available on the market377Appendix 3 Parameter clear, parameter copy and instruction code list379Appendix 4 Specification change389Appendix 4-1 SERIAL number check389Appendix 4-2 Changed functions389Appendix 5 Index391Numerics391A391B391C391D391E391F391H391I391J392L392M392O392P392R392S392T393U393W393Z393REVISIONS395Instruction Supplement(BCN-C22005-620)3961 Compatibility with the premium high-efficiency IPM motor [MMEFS(1500r/min) series] 200V class3962 Overspeed detection function (Pr. 374)3973 Compatibility with the plug-in option FR-A7NCE397Instruction Supplement(BCN-C22005-632)3981 Voltage reduction selection during stall prevention operation (Pr.154)3982 MM-EFS rated current change399Instruction Supplement(BCN-C22005-639)4001 Compatibility with the premium high-efficiency IPM motor [MM-THE4 (1500r/min) series] 200V class 75K, and 400V class 75K and 90K4001.1 Setting procedure of the premium high-efficiency IPM motor control (MM-THE4 1500r/min specification)4001.2 IPM motor control setting by selecting the parameter setting mode on the operation panel (IPM )4011.3 Initializing the parameters required to drive an IPM motor (Pr.998)4021.4 Applied motor (Pr. 71)4041.5 Specification of the premium high-efficiency IPM motor [MM-THE4 (1500r/min) series]4052 Frequency jump (6-point jump) (Pr.552)4063 SERIAL number407Instruction Supplement(BCN-C22005-644)408文件大小: 14.5 MB页数: 410Language: English打开用户手册