2700-I  WOOD INSERT (ACT)
MASONRY FIREpLACE 
USING DIRECT-CONNECT METHOD
Figure 9.1 - Installation Into Masonry Fireplace 
Direct Connect 
  Seal Option
Full Listed 
Liner Option
Mantel
SEAL DAMpER AREA  
Masonry 
Chimney 
Flue Tile
Damper 
Area
The Quadra-Fire 2700-I Insert conforms with the UL Stan-
dard for Safety 1482 and ULC S628 (Canada) in all respects, 
and is approved to UL & ULC safety standards for installa-
tion and use within a fireplace with a masonry chimney in 
accordance with NFPA 211, with a direct flue collar connec-
tion.  A starter pipe is required to reach to the bottom of the 
existing flue.
1.  Secure the fireplace damper in the open position.  If this 
cannot be accomplished, it will be necessary to remove 
the damper.
2.  Seal the damper area around the chimney liner with a 
high temperature sealant. 
.  The  chimney  should  be  examined  for  cracks,  loose 
mortar,  and  other  signs  of  deterioration  and  blockage.  
The insert should not be installed until it is determined 
that the chimney is safe for use.  Since an oversized flue 
contributes to the accumulation of creosote, the size of 
the flue should be checked to determine that it is not too 
large for the insert.  The chimney should also be checked 
to ensure it meets the minimum standard of the National 
Fire Protection Association (NFPA) Standard 211.  The 
following bullets list the more critical requirements for a 
properly constructed chimney:
   • The masonry wall of the chimney, if brick or modular 
block, must be a minimum of 4 inches (102mm) nominal 
thickness.  A chimney of rubble stone must be at least 
12 inches (05mm) thick.
  • The chimney must have a fire clay flue liner (or equiva-
lent) with a minimum thickness of 5/8 inch (16mm) and 
must be installed with refractory mortar.  An equivalent 
liner  must  be  a  listed  chimney  liner  system  or  other 
approved material.
  • A chimney inside the house must have at least 2 inches 
(51mm) of clearance to the combustible structure.  A chim-
ney outside the house must have at least 1 inch (25mm) 
clearance to the combustible structure.  Non-combustible 
fire stops must be installed at the spaces where the chim-
ney  passes  through  floors  and/or  ceiling 
(See  Figures 
7.1 and 7.2 on page 7)
NOTE:  In Canada, a full reline is required.
METAL HEAT CIRCULATING MASONRY
The Quadra-Fire 2700-I Insert conforms with the safety stan-
dard UL-1482 and ULC S628 (Canada) in all respects and is 
approved to UL & ULC safety standards for installation and 
use within a fireplace with masonry chimney, in accordance 
with NFPA  211, with a direct flue collar connection.  
Figure 9.2 Installation Into Metal Heat Circulating Showing 
Use Of Starter pipe
Listed Liner 
Mantel 
SEAL DAMpER AREA 
Fire Risk.
Inspection of Chimney:
•  Chimney must be in good condition.
•  Meets minimum standard of NFPA 211
•  Factory-built chimney must be 6 inch 
(152mm) UL10 HT.
WARNING
Fire Risk.
Do NOT pack insulation or other combustibles 
between spacers.
•  ALWAYS maintain specified clearances 
around venting and spacers.
•  Install spacers as specified.
Failure to keep insulation or other material away 
from vent pipe may cause fire.
WARNING