The  following  modifications  of  factory-built  fireplaces  are 
permissible:  1) removal of damper;  2) removal of smoke 
shelf or baffle;  ) removal of ember catches;  4) removal 
of fire grate;  5) removal of viewing screen/curtain; and,  6) 
removal of doors. 
 
NOTE:  Installation into fireplaces without a permit will 
void the listing.
The  factory-built  chimney  must  be  listed  per  UL  127  and 
meet  the  type  HT  requirements  of  UL  10.    Factory-built 
fireplace chimneys tested to UL 127-1998, may be at the 
fireplace manufacturer’s option, tested to the same criteria 
as UL 10 HT requirements.  If the chimney is not listed as 
meeting HT requirements, or if the factory-built fireplace was 
tested prior to 1998, a full height listed chimney liner must 
be installed from the appliance flue collar to the chimney 
top.  The liner must meet type HT requirements (2100ºF) 
per UL 1777.  
The liner must be securely attached to the insert flue collar 
and the chimney top.  To prevent room air passage to the 
chimney cavity of the fireplace seal the damper area around 
the chimney liner with high temperature sealant. 
The fireplace must not be altered, except that the damper 
may be removed to accommodate a direct-connect starter 
pipe or chimney liner, and external trim pieces which do not 
affect the operation of the fireplace may be removed provid-
ing they can be stored on or within the fireplace for reas-
sembly if the insert is removed.  
Direct Connect 
  Seal Option
Full Listed 
Liner Option
Mantel
SEAL DAMpER AREA  
Masonry 
Chimney 
Flue Tile
Damper 
Area
Figure 10.1 - Installation Into A Factory-Built  Zero-Clearance 
Fireplace
The Quadra-Fire 2700-I  Insert is listed to UL 1482 Standard  
and is approved for installation into listed factory-built zero 
clearance fireplaces listed to UL 127 conforming to the follow-
ing specifications and instructions:
FACTORY BUILT ZERO CLEARANCE FIREpLACE 
(USA INSTALLATIONS ONLy)
Minimum Width of Cavity Opening
28
711
Minimum Height
18-7/8
479
Minimum Depth from Front to Rear
17
42
Inches
Millimeters
The original factory-built clearance fireplace chimney cap 
must  be  re-installed  after  installing  the  approved  chim-
ney liner meeting type H.T. requirements (2100°F) per UL 
1777. The air flow of the factory-built zero-clearance fire-
place system must not be altered. The flue liner top support 
attachment must not reduce the air flow for the existing air-
cooled chimney system.
NOTE:  Refer to chimney liner manufacturer for recom-
mendations on supporting the liner.
Fire Risk.
When lining air-cooled factory-built chimneys:.
•  Run chimney liner approved to UL 1777 Type 
HT requirements (2100 degrees F)
•  Re-install original factory built chimney cap 
ONLY
•  DO NOT block cooling air openings in chimney
•  Blocking cooling air will overheat the chimney
WARNING
The  permanent  metal  warning  label  provided  must  be 
attached to the back of the fireplace, with screws or nails, 
stating that the fireplace may have been altered to accom-
modate the insert, and must be returned to original condition 
for use as a conventional fireplace.  
If the hearth extension is lower than the fireplace opening, the 
portion of the insert extending onto the hearth must be sup-
ported.  Manufacturer designed adjustable support kit can be 
ordered from your dealer.  
See page 15.
Final approval of this installation type is contingent upon 
the authority having jurisdiction.