1. Specifications
1-2
Major Component Specifications
(A)
Indoor Unit
MODEL No.
XHS2432
Source
230 - 208 VAC / 1 phase / 60 Hz
Remote  controller (Accessory)
RCS - 5HPS4U
Controller P. C. B Ass'y
CR - THS2432
Control circuit fuse
250 VAC, 3 A
Controller Ass'y
CR - 3XHS
Fan (Number … diameter)
in.
(mm)
Turbo (1…19-9/32 (490))
Fan motor
Model
SFG6X - 41A5P
Source
230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)
rpm
6 … 451
Nominal output
W
40
Coil resistance
Ω
BRW - WHT
: 114.0
,
ORG - YEL
:
66.4
(Ambient temperature 68 
°
F)
WHT - VLT
:
23.9
,
WHT - PNK
:
77.4
VLT
- ORG
:
12.4
,
YEL
- BLK
:
82.1
Safety device
Operating temperature
Open
°
F
266
±
14.4
Close
°
F
174.2
±
27
Run capacitor
VAC,
µ
F
440 V , 4 
µ
F
Electronic expansion valve
Coil
DKV - MOZS582E0
Coil resistance (at 20
°
C)
Ω
ORG - GRY
:
46
,
YEL
- GRY
:
46
RED - GRY
:
46
,
BLK
- GRY
:
46
Valve body
IKV - 24D12
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows … Fins per inch
2 … 14.9
Face area
ft.
2
(m
2
)
3.18 (0.295)
Panel
Model No.
PNR - XHS2432
Indicator Lamp Ass'y
IND - 3THS
Auto louver motor
MT8 - 3C
Auto louver motor … Rated
V, W,
rpm
240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 
°
F)
Ω
16.430 
Ω
 
±
 8 %