1. Specifications
1-3
Other Component Specifications
(A)
Indoor Unit
MODEL No.
XHS2432
Power Transformer
ATR – II174B
Rated
Primary
220 VAC, 60 Hz
Secondary
14.8 VAC 0.55 mA, 14.8 VAC 0.6 mA
Capacity
Coil resistance
Ω
WHT - WHT
:
101
,
BRN - BRN
:
0.42
(Ambient temprature 77 
°
F)
Thermistor cut off temperature
°
F
277
Thermistor (Coil sensor) : TH2, 3
PBC - 41E - S26
Coil resistance
k
Ω
14 
°
F : 23.7
,
41 
°
F : 12.1
23 
°
F : 18.8
,
50 
°
F :
9.7
32 
°
F : 15.0
,
59 
°
F :
8.0
Thermistor (Room sensor) : TH1
KTEC - 35 - S6
Coil resistance
k
Ω
32 
°
F : 16.5
,
104 
°
F :
2.7
41 
°
F : 12.8
,
113 
°
F :
2.2
50 
°
F : 10.0
,
122 
°
F :
1.8
68 
°
F :
6.3
,
131 
°
F :
1.5
86 
°
F :
4.0
,
Drain pump
WP20SL - 21
Rated
230 / 208 VAC, 12.5 W
Float switch
FS - 0218 - 102
MAX Rated (Contact rated)
50 W, DC 5V, 0.1 mA
Solenoid control valve or coil
Solenoid control valve
IKV - 24D12
Solenoid coil
DKV - MOZS582E0
Indicator Lamp Ass'y
IND - 3THS
Synchronized Motor
MT8 - 3C